11. Fire prevention during installation and use of heating appliances 12. Connecting boilers to the electrical power network 13. Wiring diagram of electromechanical regulation with extraction ventilator (DC18GD – DC50GD), valid from 12/2007 14. Obligatory standards dealing with boiler designing and boiler assembly 15.
Page 4
In case these principles are not adhered to the service life of the boi- ler body and ceramic fittingscan be substantially reduced due to the low-temperature corrosion. The boiler body can corrode within two years. CAUTION - INSTALLER SHOULD ALWAYS COMPLY WITH LOCAL PLAN- NING AND BUILDING REQUIREMENTS. www.atmos.cz 4-GB...
Instruction manual - GB 1. Intended use The environmentally friendly boilers ATMOS are designed for heating family houses, cottages, holiday houses and other similar buildings. Boilers are suitable for buildings with heat loss ranging between 19, 25, 29.8, 40 and 49 k W, depending on type. The boilers are constructed mainly for bur- ning logs.
7. Area for electronic regulation of the heating system can be used to house any type of regulation system that fits into an aperture of (92x138 mm). The electric harness is prefabricated and ready to be used for the regulation’s power supply. www.atmos.cz 6-GB...
N - boiler – filling valve 15. Cleaning lid P - pipe sleeve – sleeve for cooling loop control 17. Ignition valve pulling rod valve sensor (TS 131, STS 20) Technical data ATMOS type DC18GD DC25GD DC30GD DC40GD DC50GD 1281...
DC 50 GD 10. Heat proof shaped piece - spherical space (R + L) 14. Heat proof shaped piece - fear face CAUTION – do not turn the rear face /14/ in case of possible manipulation. www.atmos.cz 10-GB...
Example – spruce wood which has been stored for 1 year under shelter – see graph The boilers maximum output with wet fuel illustrated in the graph DC 18 GD - 13 DC 25 GD - 19 DC 30 GD - 22 DC 40 GD - 31 DC 50 GD - 39 www.atmos.cz GB-11...
Boiler output drops as low as 50 % and fuel consumption doubles. 7. Boiler bases Boiler type (mm) DC18GD DC25GD, DC30GD, DC40GD, DC50GD We recommend providing a concrete (metal) base under the boiler.
3 of the Czech standard ČSN 061008. These are appropriate for mobile installations, wooden cottages etc. 1 - Flue gas thermometer 2 - Cleaning aperture 3 - Throttle valve (draught limiter) In case of excessive chimney draught, install draught regulator (limiter) /3/. www.atmos.cz GB-13...
PVC etc.) the boilers must be put out of operation long enough before the risk occurrence. No items from flammable materials may be placed on the boilers or near them for a distance lower than the specified safe distance (more see ČSN EN 13501-1). www.atmos.cz 14-GB...
Connectors in side hoods of the boiler: Connector in the right side hood Connector in the left side hood 1 - connector for income cabel (L - brown, N - blue, PE - green/yellow) 2 - connector for exhaust fan www.atmos.cz GB-15...
95 °C (parallel connection with the flue gas thermostat). Setting the required water temperature for the building is always achieved by means of a three- way mixing valve. The mixing valve can be regulated manually or by electronic regulation, which www.atmos.cz GB-17...
For the heating system regulation we recommend regulation elements provided by the following companies: a) ATMOS ACD 01 - Eqvithermal controller set for solid fuel boilers b) KOMEXTHERM, Praha tel.: +420 235 313 284 c) KTR, Uherský Brod tel.: +420 572 633 985...
Instruction manual - GB 17. Prescribe boiler connection with an accumulation tank and electronic controller ACD01 18. Recommended boiler connection with Laddomat 21/22 or thermoregulatory valve and accumulation tanks www.atmos.cz GB-19...
If need be, a thermoregulatory valve set to a higher temperature (E.g. 72 °C) may be used. Recommended sizes of the thermoregulatory valve TV 60/65/70 °C. For boilers: DC18GD, DC25GD..........DN 25 DC30GD, DC40GD..........DN 32 DC50GD.............. DN 40 www.atmos.cz...
Place the kindling perpendicularly to the channel recess in the shaped piece so that a 2 – 4 cm gap between the recess and fuel is created; which allows the flue gas passage. Place paper or wood wool www.atmos.cz GB-23...
/22/ which automatically opens up or shuts down the valve /8/; depending on the pre-set out- going water temperature (80 - 90 °C). The output (draught) regulator adjustment should be done careful- ly because it not only regulates the output; but also protects the boiler against overheating. The setting www.atmos.cz 24-GB...
95 °C, the control flap valve must be fully closed (only providing the setscrew gap). It is always necessary to fine- tune the specified operating temperature (80 - 90 °C) utilising the mixing valves behind the boiler either manually or by electronic regulation with electric actuator. www.atmos.cz GB-25...
The lower tie-rod is used to regulation adjust the amount of the secondary air. Setting the boilers DC18GD – DC50GD Basic setting of primary air: The change of the air volume is performed by pulling or pushing the tie-rod depending on the type of fuel.
26. Procedure for the optimum boiler setting In order to achieve the best possible results in the emission measurement and the efficiency of the ATMOS boilers, the following basic conditions must be met: Fuel: Wood Type of wood: 1. Beech (the best and guaranteed fuel) 2.
Page 28
In that case you should repeat everything once more. The fuel must never be swaged. It always depends on the experience of the technician who adjusts the boiler and puts it into service. This is heating with solid fuels and it sometimes may be unpredictable. www.atmos.cz 28-GB...
The cleaning interval depends on the fuel quality (wood moisture content), heating intensity, chimney draught and other factors. We recommend cleaning the boilers once a week. Do not pull out the fireclay shaped piece /10/, /14/ when cleaning. At least once a year www.atmos.cz GB-29...
Page 30
SPHERICAL CHAMBER KERAMIK ASCHE Maximum ash quantity Cleaning the upper stoking chamber with the Sweeping the ash throught the nozzle down scraper (poker) into the bottom (cleaning) chamber. The opening in the nozzle must be always clean and free. www.atmos.cz 30-GB...
Page 31
Sample of cleaning of the flue way - bottom lid brush - upper lid. Remove flue gas brake (turbulators) during cleaning. Sample of cleaning of impeller and checking Checking and cleaning regulation of primary/ uprightness of vane on exhaust fan secondary air ratio via cleaning lid www.atmos.cz GB-31...
Cleaning doors must always be properly closed. CAUTION - Follow valid fire regulations and have in reach portable fire extinguisher. If any non-standard behavior of the boiler shut down the boiler from operation and call the service. www.atmos.cz 32-GB...
- clean the ventilator including the ducting from tar and sedi- Ventilator does not turn ments - defective capacitor - replace - defective motor - replace - bad contact in plug of motor - check - measure cable lead www.atmos.cz GB-33...
Condenser for exhaust fan UCJ4C52 - 1µF (code: S0171) /30/ CAUTION – for boilers DC18GD and DC25GD use the exhaust fan UCJ4C52 with impeller Ø 150 mm; for boilers DC30GD and DC40GD use the exhaust fan UCJ4C52 with impeller Ø 175 mm, for boiler DC50GD use the exhaust fan UCJ4C52 with close impeller Ø175 mm.
33. Environmental protection The ATMOS gasifying boilers comply with the most demanding environmental requirements and were awarded the “Environmentally friendly product” mark, in compliance with directive No. 13/2002 of the Ministry of Environment of the Czech Republic. The boilers are certified in comp- liance with the European standard EN 303-5.