Advertisement

5.4.3 Setpoint «SP1», analog / binary setpoint shift
HVAC Products
C111 and C112 are
described in chapter 8
Weather-dependent
setpoint shift:
C112: XX0X
SP1 via buttons
C111: X6XX ... XAXX
Analog setpoint shift
C111: XXX1
Sections 5.4.1 and 5.4.2
"Setpoint changeover ..."
D2 closed
dSP
0,0
D2 open
Values dSP and SP1 are entered
on the user level
Section 6.2 "User level"
Connection of binary input D2
Section 4.2 "Assignment of terminals"
¹) Only with RWF40.0X2B97
CC1B7865en
5. Operating modes
C111: XX1X ... XX3X
Outside sensor
Heating curve slope H
Setting: 0.0 ... 4.0
No
Yes
+
C111: XXX2
Binary setpoint shift
+
05.12.2002
C112: XX1X
SP1 via outside sensor
C111: XXX0
No function
SPH / oLHi
1)
SPL / oLLo
1)
Active setpoint
23/57