Sch Scaling Of Standard Signal Range End, Analog Input 1; Scl Scaling Of Standard Signal Range Start, Analog Input 1; Scl2 = 20 - Siemens RWF40.000A97 User Manual

Rwf40 series, compact universal controllers
Hide thumbs Also See for RWF40.000A97:
Table of Contents

Advertisement

8.3.1 «SCL» scaling of standard signal range start, analog input 1
Example
8.3.2 «SCH» scaling of standard signal range end, analog input 1
Example
8.3.3 «SCL2» scaling of standard signal range start, analog input 2
Example
HVAC Products
SCL = 20; SCH = 100 °C
0 mA (start) corresponds to a measured value of 20 °C
0 mA
0 °C
Value range: -1999...+9999 digit
Factory setting: 0 digit
SCH = 80; SCL = 0 °C
20 mA (end) corresponds to a measured value of 80 °C
0 mA
0 °C
Value range: -1999...+9999 digit
Factory setting: 100 digit

SCL2 = 20:

0 mA corresponds to a measured value of 20 °C, as already described
Value range: -1999...+9999 digit
Factory setting: 0 digit
CC1B7865en
20 °C
80 °C
05.12.2002
8. Configuration
20 mA
100 °C
20 mA
100 °C
45/57