Commissioning
5.3

User-specific commissioning

5-6
If other values are required than the defined parameters in the quick start menu
or in the factory settings of the 3RW44, please proceed as follows:
Under the menu item Settings (refer to Chapter 5.3.1 "Settings" main menu
item), select:
1. Select parameter set
2. Set motor data
3. Set starting mode and parameters
4. Set stopping mode and parameters
5. Set inputs and outputs
6. Check motor protection settings
7 . Save settings
Notice
The setting is buffered in a Flash E-Prom memory as soon as you change a
setting in the menu and execute it using the OK key. It is then active in the soft
starter from this moment onwards. When the control supply voltage is switched
off, this value will be canceled and the previous value be restored. In order to
permanently save the settings made in the soft starter, you must save the data
as described in Chapter 5.3.1 "Settings" main menu item and Chapter 5.4.13
Saving options.
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01