Commissioning
5.3

User-specific Commissioning

5-6
If values are required that differ from the defined parameters in the quick start
menu or in the factory settings of the 3RW44, please proceed as follows:
Under the "Settings" menu item select (refer to Chapter 5.3.1 ""Settings" Main
Menu Item"):
1. Select parameter set
2. Set motor data
3. Set starting mode and parameters
4. Set stopping mode and parameters
5. Set inputs and outputs
6. Check motor protection settings
7. Save settings
Notice
The setting is buffered in a Flash E-Prom memory as soon as you change a setting in the
menu and execute it using the "OK" button. It is then active in the soft starter from this
moment onwards. When the control supply voltage is switched off, this value will be
canceled and the previous value restored. In order to permanently save the settings made
in the soft starter, you must save the data as described in Chapter 5.3.1 ""Settings" Main
Menu Item" and Chapter 5.4.13 "Saving Options".