Installation, connection and branch layout

3.5.3 Conductor cross-sections

A1, A2, PE, L+, L-, IN1, IN2, IN3, IN4, T1, T2, 13, 14, 23, 24, 33, 34, 95, 96, 98
3RW44..-1....
3RW44..-6....
0.7 ... 0.9 Nm
∅ 5 ... 6 mm / PZ2
7 ... 8 lb·in
2 x (0.5 ... 2.5 mm²)
10
2 x AWG 20 ... 14
2 x (0.5 to 1.5 mm²)
10
2 x AWG 20 ... 16
3RW44 2.-....
2 x 10 ... 70 mm²
2 x AWG 7 ... 1/0
2 x 10 to 50 mm²
2 x AWG 7 ... 1/0
17
2 x 2.5 ... 16 mm²
2 x 2.5 ... 35 mm²
17
1 x 2.5 ... 50 mm²
2 x 10 ... 50 mm²
1 x 10 ... 70 mm²
17
2 x AWG 10 ... 1/0
1 x AWG 10 ... 2/0
4 ... 6 Nm
min 22
36 ... 53 lb·in
3-12
3RW44..-2....
3RW44..-3....
DIN 5264-A
10
10
L1, L2, L3; T1, T2, T3
3RW44 3.-....
10 ... 14 Nm
M8x25
89 ... 124 lb·in
2 x 25 ... 120 mm²
2 x AWG 4 ...
250 kcmil
2 x 16 ... 95 mm²
2 x AWG 6 ... 3/0
min. 3 x 9 x 0.8
max. 10 x 15.5 x
0.8
b ≤ 17 mm
2 x (0.25 ... 2.5 mm²)
2 x AWG 24 ... 14
2 x (0.25 ... 1.5 mm²)
3RW44 4.-....
M10x30
2 x 70 ... 240 mm²
2 x AWG 2/0 ... 500 kcmil
2 x 50 ...240 mm²
2 x AWG 2/0 ... 500 kcmil
b
14 ... 24 Nm
124 ... 210 lb·in
b ≤ 25 mm
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01