2.2.3 Example applications for heaviest starting (Class 30)

Heaviest starting Class 30 (up to 60 s with 350% I
The soft starter to be selected must be two output classes higher than the motor used
Application
Starting parameter
• Voltage ramp and current
limiting
- Starting voltage
- Starting time
- Current limit value
• Torque ramp
- Starting torque
- End torque
- Starting time
• Breakaway pulse
Stopping mode
2-4
),
n motor
Large fan
%
30
s
60
4 x I
M
20
150
60
Deactivated (0 ms)
Coasting down
Notice
These tables provide example set values and device dimensions. They serve as
information only and are not binding. The set values are application-dependent
and must be optimized during commissioning.
Soft starter dimensioning should, if required, be verified with the help of the
Win-SOFTSTARTER program or via the Technical Assistance in Section
Important notes .
Mill
Crusher
50
50
60
60
4 x I
4 x I
M
50
50
150
150
60
60
80 %; 300 ms
80 %; 300 ms
Coasting down
Coasting down
Disk saw/ribbon saw
30
60
4 x I
M
M
20
150
60
Deactivated (0 ms)
Coasting down