Circuit examples

8.1.5 3RW44 in an inside delta circuit

Main circuit
Option 1a:
1 )
400 V AC
L 1
3 / N / P E A C 4 0 0 V
, 5 0 H z
L 2
L 3
Q 1
K 1
F 3
L 1
L 2
L 3
G 1
T 1
T 2
T 3
V 1 W 1
U 1
M
3 ~
M 1
V 2
W 2
U 2
P E
Reversed direction of rotation in an inside delta circuit
Main circuit
Option 1b:
1 )
400 V AC
L 1
3 / N / P E A C 4 0 0 V
, 5 0 H z
L 2
L 3
Q 1
L 1
L 2
L 3
G 1
T 1
T 2
T 3
V 1
U 1
W 1
M
3 ~
M 1
W 2
V 2
U 2
P E
1) For permissible main and control voltage values, refer to Technical Data, pages 9-7 to 9-10.
Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset command, since an automatic restart is
executed when a start command is pending after the reset command. This especially applies to motor
protection tripping.
For safety reasons it is recommended to integrate the group fault output (terminals 95 and 96) into the
control.
8-6
Control circuit
Option 1:
L1 1/N/PE 230 V AC , 50 Hz
F2
A1
G1
PE
A2
PE
N
Caution
Observe the wiring suggestions for the inside delta circuit on the main circuit page.
Faulty connection may lead to disturbances.
1)
+24 V DC
PLC output
2)
M
Start
L+
L-
IN1
IN2
13
14
23
24
33
ON period
No action
No action
PLC-input
Reset
PTC type A or
Thermoclick
IN3
IN4
T1
T2
Group error
96
+
34
95
98
NSB0_01498
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01