Commissioning

5.2 Short set-up (Factory setting)

5.2.1
Step
1. Switch on mains voltage
2. Select the direction of rotation.
3. Select the setpoint.
4. Enable the controller.
5. The drive is now operating according to factory
setting.
5-2
820XBA1097
-
In case of condensation connect the controller to mains
voltage only after the visible humidity has evaporated.
-
The plug-in power terminals of the 820X controller must only
be connected or disconnected when no voltage is applied.
Maintain the switch-on sequence!

Switch-on sequence

-
CW rotation:
- Apply a LOW signal to terminal E4 (0...+ 3V).
-
CCW rotation:
- Apply a HIGH signal to terminal E4 (+ 12...+ 30V).
Apply a voltage 0...+ 10 V to terminal 8.
Apply a HIGH signal (+ 12...+ 30V) to terminal 28.