Huawei SmartLogger2000 User Manual page 88

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000
User Manual
Alar
m ID
1101
(2016-06-20)
Alarm
Alarm
Alarm
Severit
Sub-I
y
D
4
Abnorma
Major
1
l
Q-Contro
l
4
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Causes
Measure
currents
remote control configuration
beyond the
page and check that the start
configuratio
and end current ranges of the
n range.
AI comply with the
requirements of the power grid
company.
3. Contact the power grid
company to check whether the
command data sent is correct.
1. Check whether the cable
Under the
connections to the DI ports are
active
correct.
power Dry
2. Enter the active power Dry
contact
remote
contact remote control
configuration page and check
control
mode, the
the mapping table of the
four DI
current DI signal
ports read
configuration. Contact the
commands
power grid company to check
beyond the
the completeness of the
configuratio
combination configurations in
n.
the mapping table and check
whether the configurations
comply with the requirements
of the power grid company.
1. Verify that the port
Under the
corresponding to the AI No. in
reactive
use connects to a cable
power AI
properly. If the cable is loose,
remote
disconnected, or reversely
control
connected, reconnect it firmly
mode, the
and correctly.
AI port
receives
2. Enter the reactive power AI
currents
remote control configuration
beyond the
page and check that the start
configuratio
and end current ranges of the
n range.
AI comply with the
requirements of the power grid
company.
3. Contact the power grid
company to check whether the
command data sent is correct.
1. Check whether the cable
Under the
connections to the DI ports are
reactive
correct.
power Dry
2. Enter the reactive power Dry
contact
remote
contact remote control
configuration page and check
control
mode, the
the mapping table of the
7 Maintenance
82