User Manual
Figure 4-9 Cable connection for the terminal block
Step 4 Use a flat-head screwdriver to tighten the screws on the terminal block, as shown by (2) in
Figure 4-9.
Step 5 Insert the terminal block into the SmartLogger COM port.
Step 6 Insert the bare cable cores at the other end of the cable into a Protection port of the RS485
signal SPD, as shown by (1) in Figure 4-10.
Figure 4-10 Wiring diagram for the RS485 signal SPD
Verify that the COM+ (RS485A) port on the SmartLogger is connected to Protection port 2
or 8 on the RS485 signal SPD, and that the COM- (RS485B) port on the SmartLogger is
connected to Protection port 6 or 12 on the RS485 signal SPD.
Step 7 Use a flat-head screwdriver to tighten the screws on the Protection ports, as shown by (2) in
Figure 4-10.
----End