SmartLogger2000
User Manual
Figure 4-20 Connecting an AC power cable to the SmartLogger
Table 4-6 describes the components shown in Figure 4-20.
Table 4-6 Component
No.
1
2
3
4
(2016-06-20)
Component
Busbar A/B/C
Fuse
Knife switch
box
MCB
Each SmartLogger can be connected to a maximum of 80 SUN2000s.
If the SmartLogger is connected to the SUN2000 through an AC power cable, no RS485
communications cable needs to be connected.
After connecting cables, log in to the WebUI and enable the PLC function in the SmartLogger. For
details, see Connecting a Device. PLC describes how to configure PLC parameters for the
SmartLogger.
The port used for PLC networking is RS485-0. The recommended Baud Rate for the port is 115200
bit/s, which can provide optimal communications performance.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Item
-
Rated voltage: ≥ 500 V; rated current: 6
A
Rated voltage: ≥ 500 V; rated current: ≥
6 A; number of phases: three
Rated voltage: ≥ 500 V; rated current: ≥
6 A
4 Connecting Cables
Quantity
1 PCS
3 PCS
1 PCS
1 PCS
51