Step 6: Configuration

This section describes configuration using the local user interface pushbuttons and the preset
switches available on the unit. You can also use ValVue and a PC with a HART
®
HART
Handheld Communicator. Prior to changing the SVi1000 configuration, check the
existing configuration.
Use the procedures that follow to: run auto stops, run open stop adjustment and perform
preset or auto tune.

Auto Find Stops

To perform auto find stops:
1. Set the air action (0-7 for ATO or 8-F for ATC).
2. Press auto find stops button until green LED 1 illuminates, then release (approximately 2
seconds to turn on and release before 7 seconds). The unit goes into a Commission Process
and green LED 1 blinks until the process completes. The auto find stops process occurs.
When the process is complete, the unit automatically returns to Normal mode.
Press Cancel to abort the process and the green LED 1 goes off, the device returns to
Normal mode and no changes occur.
© 2017 Baker Hughes, a GE company, LLC. All rights reserved.
These procedures can cause the valve to move. Before proceeding
WARNING
be sure the valve is isolated from the process. Keep hands clear
from moving parts.
All calibration and configuration procedures are described using
NOTE
the SVi1000 local user interface. See "ValVue Software" on
page 16 for an overview of ValVue software functions.
Masoneilan SVi1000 Positioner Instruction Manual
®