Summary of Contents for Baker Hughes Masoneilan SVI II AP

  • Page 1 Masoneilan ™ II AP ™ Advanced Performance Digital Positioner Quick Start Guide (Rev. AB) Baker Hughes Data Classification: Public...
  • Page 2: About This Guide

    All information contained herein is believed to be accurate at the time of publication and is subject to change without notice. Copyright 2021 by Baker Hughes Company. All rights reserved. PN 055201-167 REV AB. © 2021 Baker Hughes Company. All rights reserved.
  • Page 3: Table Of Contents

    Mounting the SVI II AP on Rotary Valves ..........26 Mounting the SVI II AP on a Rotary Actuator ........26 © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 3...
  • Page 4 Checking the Air Supply ................50 Checking the Electronic Module Connections ..........50 Operational Checkout ................52 Connecting to the Current Source ............... 52 Powering Up the SVI II AP ................52 © 2021 Baker Hughes Company. All rights reserved.
  • Page 5 The Burst mode can send the following commands: ........83 Appendix D: Determining an SVI Positioner Compliance Voltage in a Control ......................Compliance Test Set-Up ................87-88 © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 5...
  • Page 6 Amended Burst mode sections and added Tri-loop configuration. AA/01-2020 Note: Rev Z was skipped. Updated ES-699 to Rev AE. Rebranded to Baker Hughes standards. Changed torque for cover from 50 to 55. AB/08-2021 ES-699 instructions removed. © 2021 Baker Hughes Company. All rights reserved.
  • Page 7 © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 7...
  • Page 8: Safety Information

    CAUTION Indicates a potentially hazardous situation, which if not avoided could result in instrument or property damage, or data loss. NOTE Indicates important facts and conditions. © 2021 Baker Hughes Company. All rights reserved.
  • Page 9: Svi Ii Ap Product Safety

    • Installed, put into service and maintained by qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmospheres. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 9...
  • Page 10: Masoneilan Help Contacts

    Changes to specifications, structure, and components used may not lead to the revision of this manual unless such changes affect the function and performance of the product. Masoneilan Help Contacts Email: svisupport@bakerhughes.com Phone: 888-SVI-LINE (888-784-5463) 10 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 11: Installation And Set Up

    Using HART eDDL and FDT-DTM technologies, ® the Masoneilan SVI II AP digital valve positioner provides interoperability with leading control systems suppliers. Figure 1 SVI II AP Digital Positioner © 2021 Baker Hughes Company. All rights reserved.
  • Page 12: Cover (I/P Module)

    Module Pneumatic Relay Figure 2 - SVI II AP Components Cover (I/P Module) Manifold Relay Electronics Module SVI II AP Cover Figure 3 - SVI II AP High Flow Components 12 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 13: Using The Quick Start Guide

    AP Instruction Manual, downloadable at valves.bakerhughes.com/resource-center. If you experience problems that are not documented in this guide refer to the SVI II AP Instruction Manual, or call your local Baker Hughes representative. Sales offices are listed on the last page of this document.
  • Page 14: Single Acting Positioner

    +5 psi. Output Supply Figure 4 - Air Ports on Single Acting Positioner Output Supply Figure 5 - SVI II AP High Flow Air Ports on Single Acting Positioner 14 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 15: Double Acting Positioner

    (see Figure 6). Output I Output II Supply Figure 6 - Air Ports on Double Acting Positioner © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 15...
  • Page 16: Pushbuttons And Local Display

    • Enter Calibration mode • Run STOPS to automatically calibrate stroke • Run autoTUNE to set dynamic response • Examine the device STATUS • Introduce manual set point changes to verify dynamic performance 16 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 17: Pushbuttons

    (Forward) (Select) (Back) Figure 7 - SVI II AP Display Pushbuttons © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 17...
  • Page 18: Pushbutton Locks And Configuration-Lock Jumper

    Access to calibrate or configure modes is not available. Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0). 18 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 19: Hardware Configuration Lock

    DD. The input to the switch can be automated by sending Device Variable 8 (DI) via CMD 9 or CMD 33 from a DCS. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 19...
  • Page 20: Valvue Software

    For more details on the use of ValVue software, refer to the ValVue User’s Guide. Contact the factory or your local representative to obtain licensing information. 20 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 21: Masoneilan Software Download

    2. Use the arrows to move through the selections. Select Download below ValVue and Figure 10 appears. Figure 10 - Opening Dialog © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 21...
  • Page 22 4. Open Windows Explorer and click the Windows Downloads folder. NOTE If you are upgrading from ValVue 2.x you must update the SQL database location to match ValVue3’s. 5. Double-click on the installer and follow the instructions to install. 22 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 23: Download And Install The Svi Ii Ap Dtm

    The results appear (Figure 11). 2. Select Download below SVI II AP DTM and Figure 12 appears. Figure 12 - Opening Dialog © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 23...
  • Page 24 For fastest installation, save the download file to your laptop/ PC. Don’t install from the website. 4. Open Windows Explorer and click the Windows Downloads folder. 5. Double-click on the installer and follow the instructions to install. 24 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 25: Mounting The Svi Ii Ap

    • Bleed air from actuator and check that valve is in its unenergized position. It is now safe to disconnect and remove any valve mounted equipment that is being replaced. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 25...
  • Page 26: Mounting The Svi Ii Ap On Rotary Valves

    Camflex for example, the shaft must be bearing on its stop to properly set up the SVI II AP Controller. During hydrostatic testing the shaft is thrust to its stop and a normally tightened packing retains it in that position. 26 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 27 10. Ensure no interference exists with the position sensor protrusion. 11. Ensure that the V-Seal makes contact with the skirt around the position sensor protrusion on SVI II AP housing. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 27...
  • Page 28: Travel Sensor Alignment

    +8000 +/- Full Closed 1500 (+45°) Any amount of 0 +/- 1000 rota tion Clockwise or Travel counterclockwise (Mid-Stroke) General Rule for other con figurations (0°) 28 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 29: Dismantling The Svi Ii Ap From Rotary Valves

    Tighten the lever screw securely. Refer to Figure 14. MS Flat head screw Figure 14 - Magnet Holder for Reciprocating Valves © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 29...
  • Page 30 M5 X 10 mm flat head screws. 9. Attach the left hand threaded rod end to the take-off rod with 1⁄4 - 20 UNC nut and thread the left hand lock nut onto the rod end. 30 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 31 13. Mount the SVI II AP to the bracket and secure with four M6 socket head cap screws. Figure 17 - Lever for Masoneilan Model 87/88 Multispring Actuator © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 31...
  • Page 32: Dismantling The Svi Ii Ap From Reciprocating Valves

    To remove the SVI II AP Controller from a reciprocating valve perform Steps 1 - 12 on page 29-31 in the reverse order. 32 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 33: Checking The Magnet

    To perform a visual inspection refer to Table 3 on page 28 and ensure that the magnet is correctly oriented for the actuator/ valve configuration. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 33...
  • Page 34: Installing The Svi Ii Ap For Double- Acting Operation

    Lever Rod- end Mount Figure 18 - 84/85/86 Actuator NOTE Mount all components snug enough to stay in place but loose enough to tap with rubber hammer into final position. 34 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 35 For bottom: hex nut regular 1/4-20 and hex screw 1/4-20 UNC x 22.2 [.88] LG. Figure 20 - Bracket Configuration Strokes .5 - 2.50” and 3-6” © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 35...
  • Page 36 Figure 22 - Lever Alignment Mount the SVI-II with M6-1 screws. Cycle the valve open to close verifying proper components movement and that rod-ends move free and clear from other components. 36 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 37: Connecting The Tubing And Air Supply

    SVI vent port. Consider both sources of natural gas when evaluating the Hazardous Classification for the area (See the Masoneilan SVI II AP Installation and Maintenance Manual for further discussion on installing an SVI II AP in a natural gas environment).
  • Page 38 SVI II AP if connected to a natural gas supply. Hazardous area clarification is the responsibility of the end user. area ventilation and other safety mea sures may be required to maintain a safe environment. 38 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 39: Installation Procedure

    (R1981) or with clean, dry, oil-free sweet natural gas supply S content not to exceed 20 ppm) (SVI II AP models SVI II AP/SD through SVI II AP/AD). © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 39...
  • Page 40: Connecting The Air Supply

    Supply pressure must be 5 - 10 psi greater than the spring range of the actuator but may not exceed the rated actuator pressure. Refer to the valve or actuator instruction manual. 40 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 41: Wiring The Svi Ii Ap

    Connect the other end of the cable to the SVI II AP. There are two threaded openings on the positioner. Use the opening with the red plastic insert. Maintain polarity + and - respectively. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 41...
  • Page 42: Wiring A Position Retransmit

    • For split range installations the output voltage must be sufficient to operate two positioners (11 V @ 4 mA, 9 V @ 20 mA) and the expected voltage drop in the cable. 42 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 43: When Wiring A Position Retransmit

    • Ensure that the position retransmit signal is connected to the control system’s analog input card. • Ensure the control loop is powered while making make measurements with a meter. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 43...
  • Page 44: Svi Ii Ap Setups

    If the valve is stable in MANUAL mode then the problem can be noise in the control system. Recheck all wiring connections and ground points. 44 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 45: Compliance Voltage In Single Drop Current Mode

    Verify that source can supply 20 mA to SVI II AP input. If 20 mA is not attainable, troubleshoot the source and set up. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 45...
  • Page 46 Supply 220 Ohms ® HART compliant control system output card ® HART Modem ValVue DPI620 Figure 23 - General Purpose and Explosion Proof Installation Figure 24 - Intrinsically Safe Installation 46 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 47: Check Out, Configuration And Calibration

    Inherent trim characteristic of the control valve; linear, equal percentage, or other. NOTE Refer to the valve data sheet or model number of con trol valve. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 47...
  • Page 48: Verifying Mounting And Linkage Adjustment

    Check that the bracket is mounted using the proper holes (refer to Table 4 on page 32). Figure 25 - Magnet Orientation for Camflex with Valve Closed 48 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 49: Using Valvue To Check Magnet Position

    60° rotation rotary valve. • At mid-travel, the value should be between –1000 and +1000 for a greater than 60° rotation rotary valve. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 49...
  • Page 50: Checking The Air Supply

    √ √ Solid State Switch #1 and #2 Optional Optional 4- 20 mA Out Position Transmit Optional Optional • Confirm the correctness of all applicable connections to the electronics module. 50 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 51 The PV (Process Variable) is not used for the SVI II AP. The Digital Input (DI) is activated using SMARTs Assistant. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 51...
  • Page 52: Operational Checkout

    Loosen the four (4) cover screws and remove the cover of the SVI II AP. Connect the +⁄- terminals to the current source + to + and - to -. See Figure 27 on page 51. Reinstall the cover and display. 52 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 53 If the SVI II AP is specified without local pushbuttons and display, local operation is not available. Configure and calibrate ® with ValVue and a HART modem. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 53...
  • Page 54: Configuration

    Higher values lead to higher PID values and quicker response and more overshoot. Once you have a preferred aggressiveness and you tune once, all future autotunes automatically use that same value, until user-changed. 54 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 55: Configuration With Pushbuttons

    13. Return to NORMAL mode. The valve moves to the value set by the current calibrator. 14. Stroke the valve through its range to verify that the movement is as desired. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 55...
  • Page 56: Configuration Menu

    If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move the SVI II AP to a different valve or make any change to the valve position linkage, you must run the find STOPS calibration again. Figure 28 - CONFIGure Menu 56 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 57: Viewing Status Messages

    CAMFXE Q 0.00 2.00 TS OFF TS ON 4.00 4.00 SIG LO SIG LO 20.00 12.00 SIG HI SIG HI English French © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 57...
  • Page 58: Calibration

    Select CALIB by pressing *. STOPS appears. The valve moves full open and back to full closed. Observe all warnings. Press * to cause the valve to stroke and to automatically calibrate valve travel. After the STOPS procedure finishes, press + twice until TUNE appears. 58 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 59: Calibration Menu

    SVI II AP to a different valve or make any change to the valve position linkage, you must run the find STOPS calibration again. Figure 29 - CALIBration Menu © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 59...
  • Page 60: Auto Tune

    Press *to begin the autoTUNE procedure. As autoTUNE proceeds, numerical messages display, indicating the procedure is working. When autoTUNE is complete, TUNE appears. Press + repeatedly until ↑ SETUP appears. Press * to return to SETUP menu; ↓ CALIB appears. 60 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 61 Figure 30 - NORMAL Operation and MANUAL Menu Structures © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 61...
  • Page 62 For example, the following message is displayed if the instrument has been serviced and the air is not connected. Process applied to the non-primary variable is outside the operating limits of the field device. 62 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 63: Proceed With The Following Steps

    14. Correct the problem (Is the air supply on?), and then go to clear status until Clear Fault codes Completed appears. 15. Press OK. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 63...
  • Page 64 This page intentionally left blank. 64 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 65: Maintenance

    AP with a solid cover and would like to upgrade to a display cover, follow the instructions below for removal and installation. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 65...
  • Page 66: Removing The Svi Ii Ap Display Cover

    SVI II AP housing. Connect the cable from the display into the LCD connector on the terminal board. Ensure that the gasket is in its groove in the housing. 66 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 67 The flange area is not corroded and the surface is not scarred. The four cover bolts are securely tightened to 55 in/lb. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 67...
  • Page 68 This page intentionally left blank. 68 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 69: Appendix A: Specifications And References

    1 G at 150 - 2000 Hz - Less than 2% of span Negligible at 30 A/m (EN61000-4-8) Magnetic Field Influence CE MARK certified to EN50081-2 and EN50082-2 © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 69...
  • Page 70 SV = Actuator Pressure (P1-P2) (N/A for standard ® HART Command #3 Mapping diagnostic version; units sends zero) TV = Supply Pressure QV = P2 for double acting units (N/A for standard diagnostic version; units sends zero) 70 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 71 300 series stainless steel Magnet Holder Corrosion Protected Anodized Aluminum 6061 T6 Pole Ring 416 stainless steel Levers 300 Series stainless steel © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 71...
  • Page 72 Always set con trol set point to 0%, and put the process control system in manual, for smooth recovery from air supply failure. Loss of Input Signal Actuator Output fails to atmosphere Output Pressure 0-150 psi (10.3 bar) max. 72 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 73 Output 1 fails to atmosphere Loss of Input Signal Output 2 fails to supply pressure. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 73...
  • Page 74 1. None 2. Position Retransmit and Limit Switches Agency Approvals 1,4 1. ATEX/FM/CSA/Intrinsic Safety & Exprf 4. ATEX (IS, NI) SVI II AP Figure 33 - SVI II AP Model Numbering 74 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 75: Hazardous Location Installation

    ES-699 instructions are available in several languages on: valves.bakerhughes.com/resource-center Spare Parts © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 75...
  • Page 76 76 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 77 © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 77...
  • Page 78 [0.362] WIDTH 2.62 [0.103] REF NO 2-110 971886124-681-0000 O-RING ID 29.87 [1.176] WIDTH 1.78 [0.0703] REF NO 2- 720020224-681-0000 O-RING ID 9.137.82 [1.498] WIDTH 1.78 [0.0703] REF NO 2- 720014540-779-0000 Instructions 78 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 79 This page intentionally left blank. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 79...
  • Page 80: Appendix B: Optional Switch Load Limits

    Figure 34 - Switch Installation Drawing without Load: Configuration Not Allowed Switch OFF Switch ON ≤ 1 V 30 VDC max. SWITCH (Switch saturation volt age) ≤ 0.200 mA 1 A max. SWITCH (Switch leakage current) 80 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 81 EMF protection to prevent voltage spikes. Load, Solenoid, Incandescent Lamp Configuration Figure 35 - Simplified Switch Installation Drawing: Correct Configuration © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 81...
  • Page 82 • If IS barrier is a combination of fuse, resistor and Zener diode then the connection is shown in Option #2. The barrier must have adequate resistance to limit inrush current, as the fuse cannot limit inrush current (see Wiring Option #2). 82 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 83: Appendix C: Burst Mode

    Choose the Burst command variables to be returned by referring to list of device variables in Table 16. Connecting the SPA with the AP Figure 37 - Burst Mode Configuration © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 83...
  • Page 84 Raw valve position Counts “ Position Total valve travel odometer (An accumulated value Strokes of 100% travel = 1 Counts “ stroke. The travel does not need to occur in one movement.) 84 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 85 Open Stop Upper limit for valve travel Percent Adjustment “ Percent of Analog Input current signal Percent “ Range in percentage © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 85...
  • Page 86 Masoneilan is not responsible for improperly wiring the TRI-LOOP. A resistor might be required on the positive leg of Channel 1 to limit the current to the TRI-LOOP. Figure 38 - Sample Tri-loop Configuration 86 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 87: Appendix D: Determining An Svi Positioner Compliance Voltage In A Control

    Read the voltage across the potentiometer, which should be > 9 VDC. This is the available system voltage at the maximum output. Table 17 lists some compliance voltage readings at positioner terminals at several currents. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 87...
  • Page 88 8 mA 10.5 V 9.5 to 10.5 V 12 mA 10 V 9 to 10 V 16 mA 9.5 V 8.5 to 9.5 V 20 mA 8 to 9 V 88 | © 2021 Baker Hughes Company. All rights reserved.
  • Page 89 This page intentionally left blank. © 2021 Baker Hughes Company. All rights reserved. Masoneilan SVI II AP Digital Positioner Quick Start Guide | 89...