Performance Specifications - Mitsubishi Electric FX2N-32CAN Hardware Manual

Communication module
Hide thumbs Also See for FX2N-32CAN:
Table of Contents

Advertisement

FX2N-32CAN Communication Module
3.3

Performance Specifications

Table 3.3: Performance Specifications
Item
Maximum
FX
-32CAN
2N
that can be
Modules
connected to the CANopen
network.
Supported Baud Rate
Number of Occupied I/O
Points
Applicable Programmable
Controller
Communication with
Programmable Controller
RUN
FROM/TO
LED Indication
Tx/Rx
ERROR
POWER
The node address can be set from 1 ~ 127. A total of 30 nodes can be
connected on each bus. By the use of repeaters or bridges, the total
number can be extended up to 127 nodes.
10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps,
800 kbps, 1 Mbps
8 points taken from either the input or output PLC I/O extension bus
FX
, FX
2N(c)
1N
FROM/TO instruction
Lit green when module is exchanging information with the CANopen
network
Lit green when module is receiving FROM/TO commands.
Lit green when CAN-interface system is in normal operation.
Lit red when communication, overflow, or general error occurs.
Lit green when the 5 V DC power supplied from main unit.
Description
Specifications 3.
3-2

Advertisement

Table of Contents
loading