Socket CAN bus is on the left side of the device. Connecting cable must be connected according
to the following designation.
For connections on the CAN bus should be only used cable LiYCY 2x0,25. Only this type of cable
gives the proper work of devices. Connections perform in a serial manner, this represents a figure
below.
Plugging in expansion modules you need to remember to correctly set the terminator, which
should be attached only at the last module throughout the system, even if the module is the only
one.
After performing all the connections you must configure the module settings. Make this by
selecting the modules that are connected to the network. More about the configuration each of
expansion modules can be found in chapter 6.5.4.1 and instruction of the enlargement module
I/O.
After finishing configuration of expansion modules to do remains only a change the system
settings. Menu is used to configuration the heating system and the possibility of settings is
dependent of number of arranged expansion modules. The table describing the functions refer to
chapter 6.5.4.2.
On the next page is a sample diagram of the system. Please note that this is only overhead view,
not containing all the elements of the system.
54
Cable connection:
L – line LOW (white)
H – line HIGH (brown)
GND – ground (grey)