Function
CH temp. for -20°C
CH temp. for 0°C
CH temp. for 10°C
CH temp. for corr. factor
Mode type
Manual Tch
Room temp. sensor
CH temp. sensor
Permanent pump
The point of the heating curve for -20°C.
The point of the heating curve for 0°C.
The point of the heating curve at 10°C.
Service
Central heating temperature correction required the
desired room temperature for 1 º C. For example, if the
correction factor is set at 6°C, room temperature set at 20°C
and measured in the room is 20.5°C then the temperature
calculated at will be reduced by 3°C.
Specifies the input mode central heating temperature: ma-
nual - the temperature of central heating inflicted manually,
weather - the temperature of central heating calculated
from the heating curve.
The desired temperature of central heating when the mode
is set to manual.
Specifies whether the system uses a room sensor.
Specifies whether the system uses a sensor heating.
Yes - the pump runs at a given temperature in the room,
reduced the temperature for heating (only with the use of
a sensor for central heating and room sensor), No - after
reaching the set temperature in the room the pump is
turned off.
Description