Unit Dimensions - York SUNLINE 2000 Manual

Single package gas / electric units and single package air conditioners
Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

530.26-TG4YI

UNIT DIMENSIONS -

3461 (136-1/4")
DCE
UNITS
3461 (136-1/4")
DCG
UNITS
8
(DCE / DCG)
1337 (52-5/8")
1337 (52-5/8")
All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.
OPENING
HOLE
(DIA.)
(mm / in.)
29 / 1-1/8" KO
A
19 / 3/4" NPS
(Fem.)
92 / 3-5/8" KO
B
76 / 3" NPS
(Fem.)
C
60 / 2-3/8" KO
43 / 1-11/16"
D
Hole
*
Opening in the bottom of the unit can be located by the slice
in the insulation.
CLEARANCES (mm / in.)
Front
914 / 36"
610 / 24" (Less Economizer)
Back
1245 / 49" (With Economizer)
610 / 24" (Less Economizer)
Left Side (Filter Access)
1372 / 54" (With Economizer)
Right Side (Cond. Coil)
914 / 36"
1
Below Unit
0 / 0"
1829 / 72" With 914 / 36" Maximum
2
Above Unit
1
Units (applicable in U.S.A. only) may be installed on combustible floors
made from wood or class A, B or C roof covering material.
2
Units must be installed oudoors. Overhanging structures or shrubs should
not obstruct condenser air discharge outlet.
NOTE:
DCE Models: Units and ductwork are approved for zero clearance to combustible mate-
rials when equipped with electric heaters.
DCG Models: A 1" clearance must be provided between any combustible
material and the supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a
confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding
those integral to the unit).
• Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet
into the building.
• Four (4) feet from electric meters, gas meters, regulators and relief equipment.
RETURN AIR
SUPPLY AIR
CONDENSER AIR
OUTDOOR AIR
(Economizer)
USED FOR
Front
Control
Wiring
Bottom
Front
Power Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)*
Horizontal Overhang
(For Condenser Air
Discharge)
Cont'd.