167791-BIM-B-0606
FIGURE 8 -
UNIT DIMENSIONS
TABLE 6: UNIT HEIGHT
Unit Model Number
DL-06
DL-07
DL-08
DL-10
DL-12
DU-06
DU-07
DU-08
DU-10
DU-12
TABLE 7: UNIT CLEARANCES
1
72"
Top
2
36"
Front
3
36"
Rear
1.
Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
2.
The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.
3.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
4.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
DETAIL A
5 - 1 / 4
1 7 - 1 3 / 1 6
V i e w o f W a l l A c r o s s f r o m
Unitary Products Group
30-11/32
X
Power
Entry
Ø 2-1/2
4-1/4
17-3/16
30-3/16
6-3/16
59
24-3/16
LEFT
X
50 3/4
42
42
50 3/4
50 3/4
42
42
42
50 3/4
50 3/4
Right
Left
4
Bottom
G a s P i p e I n l e t
B a s e
P a n
C o i l
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
Convenience
Power
Outlet
Entry
Ø 7/8
FRONT
For Drain
Dimensions
See Detail C
89
27
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
DETAIL B
12"
DETAIL C
36"
0"
NOTE: If the unit includes gas heating, locate the unit so
the flue exhaust is at least:
•
Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
•
Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.
•
Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.
See Detail
A
11-1/2
For Baserail
Dimensions
See Detail B
2 - 3 / 8
3 - 3 / 4
3 - 9 / 1 6
5 - 3 / 8
13