NOTES: 1. Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
2. Refer to Page 14 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
STATIC RESISTANCES*
WET COIL
GAS HEAT
ELECTRIC HEAT OPTIONS
ECONOMIZER OPTION
HORIZONTAL DUCT CONNECTIONS
*
Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections
(Shaded
BLOWER MOTOR AND DRIVE DATA
BLOWER
MODEL
RANGE
SIZE
kW /
(RPM)
HP
300
980 /1170 7.5 / 10
1
All motors have a nominal speed of 1450 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream
of any heating device.
2
Do NOT close this pulley below 1 turn open.
Unitary Products Group
COOLING APPLICATIONS)
(
3.78
4.25
Output
Input
ESP
Output
(KW)
(KW)
(Pa)
(KW)
5.7
6.4
249
6.6
6.1
6.9
349
7.2
6.6
7.4
448
7.7
7.0
7.9
548
8.2
8,000
9,000
Output
Input
ESP
Output
(BHP)
(KW)
(iwg)
(BHP)
7.6
6.4
1.0
8.9
8.2
6.9
1.4
9.6
8.8
7.4
1.8
10.3
9.4
7.9
2.2
11.0
EXTERNAL STATIC PRESSURE DROP
DESCRIPTION
18 KW
36 KW
54 KW
72 KW
). Add these values due to less airflow resistance.