A change of the application mode is accepted when the controller is powered-
on or while it is in emergency manual mode. If you need to change the
application mode without switching the controller off switch the controller to
Emerg.
manual off.
Binary input: REMOTE: Remote off
Related FW
3.0
Description
The controller is forced into OFF mode while this input is active and the genset is
not running. The controller will return into the previous mode after the input is
deactivated. If the genset is running, the mode does not change until it is stopped.
Use this input if you need to disable the genset temporarily from any reason
(maintenance, control from a higher-level automation system etc..).
Binary input: REMOTE: Remote MAN
Related FW
3.0
Description
The controller is forced into MAN mode while this input is active.
N
OTE
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while MAN mode is forced by this input.
Binary input: REMOTE: Remote AUT/Remote SEM
Related FW
3.0
Description
SEM mode is available in IS-NT only!
The controller is forced into AUT or SEM mode while this input is active.
N
OTE
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while AUT mode is forced by this input.
Binary input: REMOTE: Remote TEST
Related FW
3.0
Description
The controller is forced into TEST mode while this input is active. This input can
be used, among others, for following purposes:
Binary input: REMOTE: Remote off
Related FW
3.0
Description
The controller is forced into OFF mode while this input is active and the genset is
not running. The controller will return into the previous mode after the input is
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
manual, then change the application and finally switch the emergency
:
:
In combination with a timer module for periodic testing of the engine.
In combination with the input
and take over the load by one binary signal (manual switch, higher-level
automation system etc.)
Test on load
for forcing the genset to start
260