Setpoint: Derating1 end
Group
Process control
Range [units]
-32000 .. +32000 [x]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used for adjusting the end point of the Power derating 1 function,
where the gen-set nominal power is reduced to the value adjusted by setpoint
Derated1
See the chapter
N
OTE
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input PowerDerating1 is assigned.
Setpoint: Derated1 pwr
Group
Process control
Range [units]
0 .. 100 [%]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used for adjusting the final power level for the Power derating 1
function. The nominal power is not reduced below this setpoint even if the
respective analog input increases further.
See the chapter
Setpoint: Derating2 strt
Group
Process control
Range [units]
-32000 .. +32000 [x]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used for adjusting the starting point of the Power derating 2
function, where the gen-set nominal power is still 100% of the setpoint
power.
See the chapter
N
OTE
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
pwr.
Power derating
:
Power derating
Power derating
:
for details.
for details.
for details.
PowerDerating2
is assigned.
Nomin
105