ComAp IG-NT Reference Manual page 181

Compact controller for stand-by and parallel operating gen-sets inteli new technology modular gen-set controller combi – combined applications sptm, spi and mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

The currently active reserve set is selected by binary inputs
3
and
N
OTE
The reserve for stop must be always adjusted higher than the reserve for start.
Setpoint: #%LdResStrt 1
Group
Pwr Management
Range [units]
0 ..
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e.
mgmt mode
in the chapter
The currently active reserve set is selected by binary inputs
3
and
Setpoint: #%LdResStop 1
Group
Pwr Management
Range [units]
#%LdResStrt 1
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in relative mode. i.e.
mgmt mode
in the chapter
The currently active reserve set is selected by binary inputs
3
and
N
OTE
The reserve for stop must be always adjusted higher than the reserve for start.
Setpoint: #%LdResStrt 2
Group
Pwr Management
Range [units]
0 ..
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e.
mgmt mode
in the chapter
The currently active reserve set is selected by binary inputs
3
and
Setpoint: #%LdResStop 2
Group
Pwr Management
Range [units]
#%LdResStrt 2
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Load res
4. If none of these inputs is active the set #1 is selected.
:
#%LdResStop 1
[%]
= REL (%) if the reserve set #1 is active. Learn more about reserves
Reserves, minimal running
Load res
4. If none of these inputs is active the set #1 is selected.
.. 110 [%]
= REL (%) if the reserve set #1 is active. Learn more about reserves
Reserves, minimal running
Load res
4. If none of these inputs is active the set #1 is selected.
:
#%LdResStop 2
[%]
= REL (%) if the reserve set #2 is active. Learn more about reserves
Reserves, minimal running
Load res
4. If none of these inputs is active the set #1 is selected.
.. 110 [%]
Load res
power.
Load res
power.
Load res
power.
Load res
2,
Load res
Pwr
2,
Load res
Pwr
2,
Load res
Pwr
2,
Load res
181