Eaton Digitrip RMS 510 LI Instruction Manual
Eaton Digitrip RMS 510 LI Instruction Manual

Eaton Digitrip RMS 510 LI Instruction Manual

Trip unit

Advertisement

Cutler-Hammer
Instructions for Digitrip RMS 510 Trip Unit

Table of Contents

1 .0
General Description ..................... 1
1 .1
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2
Information ............................ 2
1 .3
Testing ............................... 4
2.0
UL Listed Devices ....................... 4
3.0
Principle of Operation .................... 4
3.1
General ............................... 4
3.2
3.3
Test Provisions ......................... 5
3.4
3.5
3.6
Zone Interlocking ........................ 6
4.0
Protection Settings ...................... 6
4.1
General ............................... 6
4.2
Long Delay Current Settings ............... 7
4.3
Long Delay Time Settings ................. 7
4.4
4.5
Short Delay Time Settings ................ 8
4.6
4.7
4.8
4.9
5.0
Test Procedure ........................ 10
5.1
General .............................. 10
5.2
When To Test ......................... 11
5.3
Test Provision ......................... 11
5.4
Conducting Tests ...................... 11
5.4.1
Control Power ......................... 11
5.4.2
Not Tripping the Breaker ................. 12
5.4.3
Tripping the Breaker .................... 12
6.0
6.1
General .............................. 12
6 .2
Battery Check ......................... 12
6.3
Battery Replacement. ................... 12
7.0
Auxiliary Power Module .................. 14
8.0
9.0
References ........................... 15
9.1
9 .2
Breakers ........................... 15
9.3
9.4
Breakers ........................... 15
Effective May 1997, Supersedes I.L. 29-885A dated Septem-
Page
DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN­
TENANCE ON EQUIPMENT WHILE IT IS ENERGIZED.
DEATH OR SEVERE PERSONAL INJURY CAN
RESULT FROM CONTACT WITH ENERGIZED EQUIP­
MENT. ALWAYS VERIFY THAT NO VOLTAGE IS
PRESENT BEFORE PROCEEDING WITH THE TASK,
AND ALWAYS FOLLOW GENERALLY ACCEPTED
SAFETY PROCEDURES. CUTLER-HAMMER IS NOT
LIABLE FOR THE MISAPPLICATION OR MISINSTAL­
LATION OF ITS PRODUCTS.
It is strongly urged that the user observe all recommen­
dations, warnings and cautions relating to the safety of
personnel and equipment, as well as general and local
health and safety laws, codes, and procedures.
The recommendations and information contained herein
are based on experience and judgment, but should not
be considered to be all-inclusive or covering every appli­
cation or circumstance which may arise. If you have any
questions or need further information or instructions,
please contact your local representative, or the Customer
Support Center for the type of circuit breaker you have:
Circuit
Breaker
Type
DS/DSL
SPB
Series C ® R-Frame

1 .0 GENERAL DESCRIPTION

1 .1 Protection

The Digitrip RMS 5 10, illustrated in Fig. 1, is a custom
application specific integrated circuit based trip unit suit­
able for use in types DS and DSL low voltage AC power
circuit breakers and type SPB Systems Pow-R circuit
breakers and Series C ® R-Frame molded case circuit
breakers.
The Digitrip RMS 5 10 provides true RMS current sensing
for proper correlation with thermal characteristics of con­
ductors and equipment. Interchangeable rating plugs are
provided to establish the continuous current rating of
each circuit breaker.
I.L. 29-8858
A
WARNING
Call
Send to
Telephone
FAX
Number
Number
(412) 937-6029
(412) 937-6396
(412) 937-6029
(412) 937-6396
(412) 937-6490
(412) 937-6010

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Digitrip RMS 510 LI

  • Page 1: Table Of Contents

    Cutler-Hammer I.L. 29-8858 Instructions for Digitrip RMS 510 Trip Unit Table of Contents Page WARNING 1 .0 General Description ..... 1 1 .1 Protection ......1 Information ......
  • Page 2: Information

    I.L. 29-8858 Page 2 The Digitrip RMS 5 10 Trip Unit is completely self-con­ Note*: RMS Digitrip Type LI, LS, and LSI trip units tained and when the circuit breaker is closed, requires no can be applied on 3-pole or 4-pole circuit breakers external control power to operate its protection sys­...
  • Page 3 I.L. 29-8858 Page 3 Fig . 2 .1 Long Time/Instantaneous Protection (U) Fig . 2 .3 Long Time/Short Time/Instantaneous Protection (LSI) Fig . 2 .2 Long Time/Short Time Protection (LS) Fig . 2 .4 Long Time/Instantaneous/Ground Protection (UG) Effective May 1997...
  • Page 4: Testing

    I.L. 29-8858 Page 4 Fig . 2 .5 Long Time/Short Time/Ground/Protection Fig . 2 .6 Long Time/Short Time/Instantaneous/Ground (LSG) Protection (LS/G) The Digitrip RMS 510 Trip unit provides three basic func­ 1 .3 Testing tions: Protection, Information and Testing. A typical trip To test the trip unit, use the integral test panel.
  • Page 5: Trip And Operation Indicators

    I.L. 29-8858 Page 5 r------------------- -------------- ------------------- (Li N E/UPPEI'I) Protection A:i �:� �;��� ) Input Function s.. t ting By SwItches and PushbunoRR 1 1 1 SeeSaction4. RED, » II Lighted __ __ _ Indicat8sCeuee OfTRIP(Locatod On Front Panel! 1.2.
  • Page 6: Override (Fixed Instantaneous)

    I.L. 29-8858 Page 6 Notes: Note: If a breaker (M) receives a Zone Interlocking signal from another breaker (F), but the fault current This switch has eight (8) positions, and seven (7) level is less than the trip unit setting for breaker (M), of them show in the window, while ONLY "DIS"...
  • Page 7: Long Delay Current Settings

    I.L. 29-8858 Page 7 4.2 Long Delay Current Setting allow for the fact that the load circuit temperature is already higher than normal, due to the prior There are eight (8) available Long Delay Settings, as overload condition. Each time an overload condi­ "// illustrated in Fig.
  • Page 8: Short Delay Current Settings

    I.L. 29-8858 Page 8 LOT will reset itself. You can of course, manually range from 2 to 6 times (In) the rating plug value, and the clear the LOT (or any other trip indication) at any other two settings are "M1" or "M2" times (In). The values time, by pushing the "PUSH to RESET"...
  • Page 9: Ground Fault Time Delay Settings

    I.L. 29-8858 Page 9 TABLE 1 GROUND FAULT CURRENT SETTINGS Available Settings GROUND FAULT CURRENT SETTINGS (AMPERES)!, 2,2.5,3,4, M" M, � 5,6, ettin Inst. --� In Multiples of ill X 'n Rating Plug Amperes {I n > ® :ii) ___ _ �...
  • Page 10: Test Procedure

    I.L. 29-8858 Page 10 Available "Test Amps" Settings Breaker Trips <D "6T" = Phase Current Test at 6xl n and TRIPS breaker; 10" [ill <D Test Amps Gnd Fault "1.2.3.8 or =Phase Time !J:, x In Current Test - NO reaker Sec.
  • Page 11: When To Test

    I.L. 29-8858 Page 1 1 5.2 When To Test the current is not less than 10% of the breaker frame (or current sensor) rating; Tests can be conducted with the breaker in the "con­ be sure the "GREEN" Unit Status LED (in nected"...
  • Page 12: Not Tripping The Breaker

    I.L. 29-8858 Page 12 the APM it may appear as if the trip unit does not trip unit will not execute your instructions to Test respond until the current is well-above the set value, itself, when the load current exceeds 50% of fr.) leading the tester to believe there is an error in the Place the "Test Amps"...
  • Page 13 I.L. 29-8858 Page 13 Note: The battery can be replaced at any time, even obtained from the following companies under their type while the circuit breaker is in service, without affect­ designation indicated: ing the operation of the circuit breaker or its protec­ Company Model tion function.
  • Page 14: Auxiliary Power Module

    I.L. 29-8858 Page 14 7.0 AUXILIARY POWER MODULE ble), " and 2) "In (Rated I) current value. The Auxiliary Power Module or APM (Cat No. PRTAAPM), illustrated in Fig. 7, is an encapsulated This latter value, (In) is the basis for the trip unit current power supply that requires a 120 Vac input at either 5 0 or settings: 60 Hz.
  • Page 15: References

    I.L. 29-8858 Page 15 Master Connection Diagram for Series C ® 9.0 REFERENCES I.L. 29C714 R-Frame Circuit Breaker 9.1 Digitrip RMS Trip Assemblies APPENDIX A ZONE INTERLOCKING I.L. 29-885 Instructions for Digitrip RMS 510 Trip Unit Assume a ground fault of 2000 Amperes occurs and I.L.
  • Page 16 I.L. 29-8858 Page 16 tection) Wiring to be twisted pair of AWG No. 1 4 to AWG No. 20. Main 3200 A Route Zone Interlocking wiring sepa­ rate from power conductors. DO NOT GROUND any Zone Interlock 0.5 Sec Wiring. 1200 A The maximum distance between first and last zone is 250 feet (1 1 0 m).
  • Page 17 I.L. 29-8858 Page 17 NOTES Effective May 1997...
  • Page 18 I.L. 29-8858 Page 18 NOTES Effective May 1997...
  • Page 19 I.L. 29-8858 Page 19 NOTES Effective May 1997...
  • Page 20 I.L. 29-8858 Page 20 This instruction booklet is published solely for information purposes and should not be considered all inclusive. If further information is required, you should consult Cutler-Hammer. Sale of product shown in this literature is subject to terms and conditions outlined in appropriate Cutler-Hammer Inc.

Table of Contents