Description Of Operation; Operating States And Sequences; About Operating States; Operating State Descriptions - McQuay MicroTech II Operation Manual

Applied rooftop unit controller space comfort control (scc) used with mcquay models: rps, rfs, rcs, rpr, rfr, rdt, rds, rar and rah
Hide thumbs Also See for MicroTech II:
Table of Contents

Advertisement

Description of Operation

The following sections describe how the various zone (or
space comfort) control unit processes function to maintain
temperature, ventilation and pressure control. The "Operat-
ing States and Sequences" section provides an overall
description of unit operation. The subsequent sections pro-
vide detailed descriptions of the various control processes
and how the related set points and parameters affect them.
The related set points and parameters are listed at the begin-
ning of each applicable sub-section. The default keypad pro-
grammable values are shown in italic letters.
Note:
Not all the features covered in this section apply to
all units depending on the specific unit options. The
applicable items should be read and understood
before making set point or control parameter
changes.

Operating States and Sequences

About Operating States

Operating states define the current overall status of the roof-
top unit. The operating state can be displayed and the unit
operating condition can be quickly determined by viewing
the UnitStatus= parameter in the System menu. Each operat-
ing state summarizes the following information:
Discharge and return/exhaust fan status
l
Outdoor air damper status
l
Return/exhaust airflow capacity
l
Heating system status
l
Cooling system status
l
Fan Operation Output status (MCB-BO3)
l
Table 28: Operating States
Operating
Discharge/
Exhaust
State
Return Fans
Off
Off
Startup
Off
Recirc
On
Fan Only
On
Cycling
Econo
On
Cycling
Cooling
On
Cycling
MWU
On
Heating
On
Cycling
Min DAT
On
Cycling
UnocEcon
On
Cycling
UnocClg
On
Cycling
UnocHtg
On
a.
When the OA Ambient= parameter indicates "Low", the economizer outdoor air dampers is fully open; when the OA Ambient= parameter
indicates "High", the economizer outdoor air dampers are at Eff Min OA Pos= value.
When the OA Ambient= parameter indicates "Low", the outdoor air dampers are fully open; when the OA Ambient= parameter indicates
b.
"High", the outdoor air dampers are fully closed.
OM 138
Return
OA
Airflow
Fan
Dampers
Capacity
Off
Closed
0%
Off
Closed
0%
Off
Closed
Modulating
Minimum
Modulating
Modulating
Modulating
Minimum or
Modulating
a
Open
Off
Closed
Modulating
Minimum
Modulating
Minimum
Modulating
Modulating
Modulating
Closed or
Modulating
b
Open
Off
Closed
Modulating
Table 28 shows the all the normal operating states and the
status information they summarize

Operating State Descriptions

The following sections describe each of the unit operating
states.
Off
There are five different Off operating states. In any of the
Off operating states the unit is shut down. The fans are off
and the outdoor air dampers are closed, any fan inlet vanes
or VFD is driven to 0%. Cooling and heating are disabled.
The Fan Operation Output (MCB-BO3) is open.
The five different Off operating states are described in the
following sections:
Off Unoc . Generally, the unit operating state is Off Unoc
when it the unit is being scheduled on and off by a time clock
function and the time schedule indicates an unoccupied
period. Specifically, the operating state is Off Unoc when the
Occupancy= parameter indicates "Unocc" and none of the
unoccupied unit operation functions are active. For details
regarding the Occupancy= parameter refer to "Occupancy"
on page 46. For details regarding unoccupied unit operation
functions refer to "Unoccupied Control" on page 89.
Off Net . The unit operating state is Off Net when the Appl
Mode= parameter is set to "Off" via a network signal and the
Ctrl Mode= parameter is set to "Auto." For detailed infor-
mation regarding the Appl Mode= and Ctrl Mode= parame-
ter, refer to "Auto/Manual Operation" on page 45.
The unit operating state is also Off Net when the Emerg
Override= parameter in the Occupancy menu is set to "Off."
Refer to "Emergency Override" on page 48.
Exhaust
Mechanical
Heat
Airflow
Cooling
Enabled
Capacity
Enabled
0%
No
No
0%
No
No
0%
No
No
Modulating
No
No
Modulating
No
No
Modulating
No
Yes
0%
Yes
No
Modulating
Yes
No
Modulating
Yes
No
Modulating
No
No
Modulating
No
Yes
0%
Yes
No
Fan Output
(MCB-BO3)
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
61