Dräger REGARD Instructions For Use Manual page 26

Gas detection system, relay module, relay display card atex version
Hide thumbs Also See for REGARD:
Table of Contents

Advertisement

26
Set relays energise on alarm or normally energised
04–4 RLY ENER
• Select 04-4
• Enter
Current setting:
• Select NORM or ENER, e.g. ENER*
• Select next/previous relay and repeat
• Exit command
* NORM = Normally energised
Set communications checksum
The relay display card must use the same communications checksum for RS-485
communications as the rest of the Regard system. Use CRC whenever possible.
52-6 CHECKSUM
• Select 52-6
• Enter command
Current setting:
• Select mode, e.g. CSUM
• Exit command
Quit command mode
00-0 QUIT
• Select 00–0
• Enter
• Select YES
• Enter
Card exits command mode
REGARD Relay Module & Relay Display Card (ATEX version)
ENER = Energise on alarm
PRESS
DISPLAY
04-4:001
R
RLY ENER
then
001:NORM
001:ENER
005:ENER
R
04-4:005
PRESS
DISPLAY
52-6
R
CHECKSUM
then
CRC
CSUM
R
52-6
PRESS
DISPLAY
00-0
R
QUIT:NO
QUIT:YES
R
001:CLR
Issue 1 – July 2003