This parameter could be set only by
authorized service technique!
Operation of the boiler in HT is possible
only on the basis of permission of
official electricity network distributor!
P23-Selection of maximal output for heating of
TUV (sanitary water) with high price tariff (HT), (0
- 22,5 kW).
Using this parameter you are able to limit output of
the boiler for heating into the storage water tank TUV
(sanitary water) with high price tariff (HT).
Value 0 to 22.5 maximum power output in kW, the
step according to the mounted heating rod type (see
Parameter Tab., P35).
This parameter could be set only by
authorized service technique!
Operation of the boiler in HT is possible
only on the basis of permission of
official electricity network distributor!
P24-Selection of maximal output for heating of
whole system with low price tariff (NT), (0- 22, 5
kW)
Using this parameter you are able to limit output of the
boiler for heating system during its operation with low
price tariff (NT) HDO (mass remote control) signal.
Value 0 to 22.5 maximum power output in kW, the
step according to the mounted heating rod type (see
Parameter Tab., P35).
This parameter could be set only by
authorized service technique!
P25-Selection of maximal output for heating of
TUV (sanitary water) with low price tariff (NT),
(0 - 22, 5 kW)
Using this parameter you are able to limit output of the
boiler for heating into the storage water tank TUV
(sanitary water) with low price tariff (NT) HDO (mass
remote control) signal.
Value 0 to 22.5 maximum power output in kW, the
step according to the mounted heating rod type (see
Parameter Tab., P35).
This parameter could be set only by
authorized service technique!
P26-Selection of lightening relay function in 1st
level (0 - 12, 5 kW)
Using this parameter you are able to set how the
nominal output will be lighted in case of the signal of 1st
level from the lightening relay placed in consumer
board unit.
Value 0-half the max. power output, a step by the set
value of parameter P35.
This parameter could be set only by
authorized service technique!
P27-Selection of lightening relay function in 2nd
level (0- 12, 5 kW)
Using this parameter you are able to set how the
nominal output will be lighted in case of the signal of
2nd level from the lightening relay placed in consumer
board unit.
Value 0-half the max. power output, a step by the
set value of parameter P35.
This parameter could be set only by
authorized service technique!
P28- Selection of manual switching on of HDO
(mass remote control) signal
Using this parameter it is possible to simulate the HDO
signal (activation of low price tariff NT). This parameter
is automatically deactivated after 10 min. This
parameter is only for service and after sales service
purposes including boiler setting.
HDO (mass remote control) it is not active.
O.K. HDO is activated after its confirmation for 10 min.
This parameter could be set only by
authorized service technique!
P29- Selection of safety PIN code
Using this parameter it has to be set PIN SIM card
inserted in GSM mode. In case that SIM card is not
by PIN protected, this number could each one.
The value xxxx four places number.
For this possibility of remote GSM control
of the boiler it is necessary to buy a GSM
model!
If you insert the wrong number of PIN
then you could block the SIM card!
P30-Selection of the user No. 1 responsible for
remote GSM communication with the boiler
Using this parameter it has to be inserted GSM mobile
phone number of the user responsible for remote GSM
communication with the boiler through SMS. The
number has to be inserted in the international number
format and if the number is shorter than 13 places then
it is necessary to insert for free ending place "N".
The value 0, 1, 2, ...9, N + - marking of phone number
25