ESIE16-03B
|
Part 2. Troubleshooting
Possible cause
Faulty radiating fin thermistor.
Faulty outdoor unit PCB in which radiating
fin thermistor is connected.
2.2.2.23. "PJ-00" – Capacity setting abnormality
Trigger
Outdoor main PCB detects a defective
capacity in EEPROM.
Possible cause
Position of PCB dip switches are not OK.
Faulty outdoor unit main PCB.
Faulty capacity adapter on outdoor PCB.
22/08/16
|
Version 1.1
SA R32 Sky-Air RZAG-L
Check
Check radiating fin thermistor (see
"Refrigerant thermistors" on page
Check if the HAP LED is blinking in regu-
lar intervals (see
"Main PCB" on page
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Effect
Unit will stop operating.
Check
Check if dip switches are set to default
(OFF) position.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Check if the correct adapter is installed.
Check if the correct spare part is installed.
2.2. Error based troubleshooting
Corrective action
Replace radiating fin thermistor when
57).
required.
Restore the power to the outdoor main
55).
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals
(see
"Replacing main PCB" on page
Reset
Manual reset via user interface.
Power supply reset.
Corrective action
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals
(see
"Replacing main PCB" on page
Adjust capacity adapter when required.
89).
89).
Page 39