Daikin SA R32 Sky-Air RZAG-L Service Manual page 111

Table of Contents

Advertisement

ESIE16-03B
|
Part 5. Appendix
Graph 2
Target evaporating temperature control when "low humidity application" is selected. Field setting 16(26)-2-03:
Graph 3
Target evaporating temperature control when "low humidity application + freeze up operation prevention" is selected. Field setting 16(26)-2-04:
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise of temperature after thermostat OFF, the thermostat control will be changed when
using field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON
∆Trs ≥ 0.5°C (No change from standard setting)
Thermostat OFF
∆Trs ≤ -2.0°C for 5 minutes continuously.
∆Trs ≤ 4.5°C
Capacity
When "low humidity application" is selected. Field setting 16(26)-2-03:
Indoor Temp. (°C-WB)
Outdoor
Temp.
11
14
(°C-DB)
Capacity (% of standard point)
-15
0.62
0.76
-10
0.62
0.76
-5
0.62
0.81
0
0.62
0.81
22/08/16
|
Version 1.1
SA R32 Sky-Air RZAG-L
Te target acceptable area
Remote controller setting temp.
Te target
Te target limited ≤ 20°C
(°C)
(to protect the comp.)
Te (see note) target acceptable area
■ Indoor temp. > setting → Te target down
■ Indoor temp. < setting ← Te target up
Te target limited ≥ 0°C
Freeze protection
(40 min. integrated coil temp. ≤ -1°C)
Te target acceptable area
Remote controller setting temp.
Te target
Te target limited ≤ 20°C
(°C)
(to protect the comp.)
Te (see note) target acceptable area
■ Indoor temp. > setting → Te target down
■ Indoor temp. < setting → Te target up
Te target limited ≥ 2°C
(not to freeze)
Freeze protection
(40 min. integrated coil temp. ≤ -1°C)
16
18
19
0.86
0.95
1.00
0.86
0.95
1.00
0.91
1.01
1.06
0.91
1.01
1.06
Indoor Temp
(°C DB)
Indoor Temp
(°C DB)
20
22
24
1.02
1.07
1.11
1.02
1.07
1.11
1.16
1.21
1.26
1.16
1.21
1.26
5.2. Detailed information setting mode
Page 111