When using the "LH settings" outside the "Low Humidity Area" there is an increased risk of ice accumulation on the indoor coil or water blowing out from the indoor unit.
Field Setting
Compressor control
Freeze protection function
Start
End
Parameters
FCQG
A
-5°C
Graph 1
Target evaporating temperature control in case of factory setting 16(26)-2-01:
Page 110
SA R32 Sky-Air RZAG-L
Factory setting
16(26)-2-01
The compressor frequency is controlled in function of the target evaporating temperature.
The target evaporating temperature is controlled in function of the cooling load.
Minimum target Te = 2°C
See graph 1
Te ≤ -1°C for 40 minutes accumulated
OR
Te ≤ A°C for 1 minute continuous (Indoor deci-
sion)
Te > 7°C for 10 minutes continuously. (Indoor
decision)
FHQG
-3°C
Te target acceptable area
Remote controller setting temp.
Te target limited
≤ Indoor temp. – 11°
(not to rising wetbulb)
Te (see note) target
acceptable area
■ Indoor temp. > setting
→ Te target down
■ Indoor temp. < setting
→ Te target up
Te target limited ≥2°C
(not to freeze)
Freeze protection
(40 min. integrated coil temp. ≤-1°C)
Low humidity application setting
16(26)-2-03
Minimum target Te = 0°C
See graph 2
Te ≤ -1°C for 40 minutes accumulated
OR
Te ≤ -3°C for 1 minute continuous (Outdoor
decision)
Te > 7°C for 3 minutes continuously
OR
Te > 4°C for 20 minutes continuously (Outdoor
decision)
Te target limited ≤20°C
(to protect the comp.)
Te target limited
≥ Indoor temp. – 25°
(not to sweat)
Indoor Temp
(°C DB)
5.2. Detailed information setting mode
Low humidity application + freeze up
operation prevention
16(26)-2-04
Initial minimum target Te = 2°C, but can be
changed in function of actual Te, to avoid
freeze up activation:
Te ≤ -1°C for 20 minutes accumulated =>
Change target Te ≥ 5°C
Te ≤ -1°C for 30 minutes accumulated =>
Change target Te ≥ 8°C
See graph 3
Te ≤ -1°C for 40 minutes accumulated
OR
Te ≤ A°C for 1 minute continuous (Outdoor
decision)
Te > 7°C for 3 minutes continuously
OR
Te > 4°C for 20 minutes continuously (Outdoor
decision)
22/08/16
|
Version 1.1