Part 4. Maintenance; Indoor Unit; General Maintenance Indoor Unit - Daikin SA R32 Sky-Air RZAG-L Service Manual

Table of Contents

Advertisement

ESIE16-03B
|

Part 4. Maintenance

This part contains the following chapters:

Indoor unit ............................................................................................................................................................................................95

Outdoor unit..........................................................................................................................................................................................96
4.1. Indoor unit

4.1.1. General maintenance indoor unit

1.
Optimal operation conditions
Differential between suction temperature
and discharge temperature
DB
WB
2.
Correlation of air-conditioner's operation status, pressure and running current
COOLING
Dirty air filter
Short circuit of air inlet/outlet
Air mixed in refrigerant
Water mixed in refrigerant
Dirt mixed in refrigerant
Refrigerant shortage (gas)
Unsatisfactory compression
* Water in the refrigerant freezes inside the electronic expansion valve and is basically the same phenomenon as pump down.
** Dirt in the refrigerant clogs filters inside the piping and is basically the same phenomenon as pump down.
*** Pressure differential between high and low pressure becomes low.
22/08/16
|
Version 1.1
SA R32 Sky-Air RZAG-L
Part 4. Maintenance
Cooling
8~18°C
27°C
19°C
Low pressure
Lower
Lower
Higher
Lower*
Lower**
Lower
Higher***
Heating
14~30°
20°C
NA
High pressure
Lower
Lower
Higher
Lower
Lower
Lower
Lower
4.1. Indoor unit
Running current
Lower
Lower
Higher
Lower
Lower
Lower
Lower
Page 95