Samsung AVMKH020EA0 Service Manual page 191

System air conditioner dvm series
Hide thumbs Also See for AVMKH020EA0:
Table of Contents

Advertisement

8
Troubleshooting
8-2-10. In removing frost
Outdoor unit display
Indoor unit display
Judgment method
Causes
8-2-11. Protection control of condensation ratio
Outdoor unit display
Indoor unit display
Judgment method
Causes
✳Condensation ratio = (High pressure+1.03)/(Low pressure+1.03)
✳Stop the compressor when the condensation ratio is more than 8.5 for 10 minutes
(Operation)
(Timer)
- In removing frost
- Not a defect
(Operation)
(Timer)
- Stop the compressor at the continual operation over 10 minutes with the state of 8.5 over of the
-
compression rate.
- Start on the low temperature
- Leakage or over shortage of refrigerant
- Compressor unloading failure
- Service valve closing/EEV closing
- 190 -
(Fan)
(Filter)
(Removing frost)
(Fan)
(Filter)
(Removing frost)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Avmkh032ca0Avmkh040ca0Avmkc020ea0Avmkc020ca0Avmkh020ca0Avmkh026ea0 ... Show all

Table of Contents