Samsung AVMKH020EA0 Service Manual page 251

System air conditioner dvm series
Hide thumbs Also See for AVMKH020EA0:
Table of Contents

Advertisement

8
Troubleshooting
8-2-68. OIL temperature sensor error (open / short)
Outdoor unit display
Indoor unit display
Judgment method
Causes
Is separated the outdoor oil
temperature sensor connecter from
Detach the outdoor oil temperature sensor
connecter from PCB, and measure the
resistance value between the both terminals.
Yes
Is the resistance value far from the
temperature table?
Restart after PCB exchange.
,
,
(Operation)
(Timer)
- When opening or shorting of outdoor oil temperature sensor
- Open or short of the corresponding sensor
PCB?
No
No
,
(Fan)
(Filter)
(Removing frost)
Yes
Restart after connecting a connecter to PCB.
Temperature
Yes
Replace the outdoor oil temperature
sensor because it is defect.
- 250 -
Resistance
(˚C)
(kΩ)
130
8.9
120
11.2
100
18.5
80
32
60
59
25
200
20
242
10
362
0
553
-10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Avmkh032ca0Avmkh040ca0Avmkc020ea0Avmkc020ca0Avmkh020ca0Avmkh026ea0 ... Show all

Table of Contents