Operation With Residual Current Devices (Rcd) - Siemens SINAMICS G120 Hardware Installation Manual

Power module
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Connecting

4.3 Operation with Residual Current Devices (RCD)

4.3
Operation with Residual Current Devices (RCD)
Operation with Residual Current Devices (RCD)
If an RCD (also referred to as an ELCB or a RCCB) is fitted, the Power Module will operate
without nuisance tripping provided that:
● A type B RCD is used.
● The trip limit of the RCD is 300 mA.
● The neutral of the supply is grounded.
● Only one Power Module is supplied from each RCD.
● The output cables are less than 50 m (164 ft) screened or 100 m (328 ft) unscreened.
If no RCD is used, the touch protection can be achieved by double insulation or by
separating the Power Module from the mains system using a transformer.
38
Hardware Installation Manual, 07/2009, A5E00807525B AD
Power Module PM240

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pm240

Table of Contents