Siemens SINAMICS G120 Hardware Installation Manual page 90

Power module
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Accessories
7.1 Reactor and filter
Installing the output reactor as lateral mounting component
The output reactors for Power Modules with a rated power (HO) of more than 11 kW have to
be mounted laterally.
Figure 7-7
For more information see http://support.automation.siemens.com/WW/view/en/22103628
Technical specifications of the output reactors
The major electrical specification of the output reactors is the same as for the suitable Power
Module. This applies to:
● voltage
● rated current
The maximum permissible output frequency of the Power Module is 150 Hz when an output
reactor is used – the pulse frequency must not exceed 4 kHz.
The admissible ambient conditions of the output reactors are the same as for the suitable
Power Module. This applies to:
● storage and transport temperature
● operating temperature
● relative humidity
● shock and vibration load
90
Connecting the output reactor as lateral component
Hardware Installation Manual, 07/2009, A5E00807525B AD
Power Module PM240