Accessories
7.1 Reactor and filter
Mounting base components
Many system components for the Power Modules are designed as base components, that is,
the component is mounted on the cabinet wall and the Power Module above it in a space-
saving construction. Up to two base components can be mounted above one another. Every
further system component has to be mounted laterally.
Figure 7-1
Table 7- 1
Power Module frame size
FSA and FSB
0.37 kW ... 4 kW
FSC
5.5 kW ... 11 kW
78
Mounting base components
Possible combinations of two base components
Base component on ...
... position 1
Line reactor
Line filter
Line reactor
Line filter
... position 2
Output reactor
Sine-wave filter
Braking resistor
Line reactor
Output reactor
Sine-wave filter
Braking resistor
Output reactor
Sine-wave filter
Line reactor
Output reactor
Sine-wave filter
Hardware Installation Manual, 07/2009, A5E00807525B AD