Siemens SINAMICS G120 Hardware Installation Manual page 96

Power module
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Accessories
7.1 Reactor and filter
Installing the sine-wave filter as lateral mounting component
The sine-wave filter for Power Modules with a rated power (HO) of more than 11 kW has to
be mounted laterally.
Figure 7-9
For more information see http://support.automation.siemens.com/WW/view/en/29522775
Technical specifications of the sine-wave filter
The major electrical specification of the sine-wave filter is the same as for the suitable Power
Module. This applies to:
● voltage
● current
The maximum permissible output frequency of the Power Module is 150 Hz when a sine-
wave filter is used – the pulse frequency must not exceed 8 kHz.
The admissible ambient conditions of the sine-wave filter are the same as for the suitable
Power Module. This applies to:
● storage and transport temperature
● operating temperature
● relative humidity
● shock and vibration load
96
Connecting the sine-wave filter as lateral component
Hardware Installation Manual, 07/2009, A5E00807525B AD
Power Module PM240