5.16
PXD24 OU7-24, OU7-24Z & OU7-24T R410A
5.16.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
LEGEND
TC
Total Cooling Capacity, kW
SC
Sensible Capacity, kW
PI
Power Input, kW
WB –
Wet Bulb Temp., (
DB
Dry Bulb Temp., (
ID
Indoor
OU
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
SM PXD 1-E.3 GB
PERFORMANCE DATA & PRESSURE CURVES
ENTERING AIR WB/DB ID COIL ( °C)
DATA
15/21
TC
7.20
SC
5.02
1.61
PI
TC
6.97
4.92
SC
1.75
PI
TC
6.59
4.80
SC
1.89
PI
6.16
TC
4.65
SC
2.04
PI
TC
5.71
4.42
SC
2.20
PI
5.19
TC
SC
4.16
2.37
PI
TC
4.50
3.84
SC
2.59
PI
o
C)
o
C)
CONTENT
17/24
19/27
21/29
7.46
7.63
5.24
5.44
1.61
1.62
7.34
7.57
5.19
5.41
1.75
1.76
7.12
7.48
5.09
5.37
1.90
1.91
6.71
7.25
4.94
5.25
2.08
2.07
6.19
6.83
4.74
5.13
2.23
2.27
5.65
6.16
4.48
4.85
2.41
2.45
4.92
5.41
4.11
4.43
2.63
2.69
23/32
7.81
7.93
5.58
5.68
1.62
1.63
7.75
7.92
5.56
5.67
1.77
1.77
7.71
7.89
5.52
5.63
1.93
1.94
7.51
7.73
5.40
5.51
2.10
2.12
7.17
7.51
5.28
5.38
2.29
2.30
6.74
7.09
5.01
5.11
2.48
2.50
5.98
6.44
4.58
4.68
2.73
2.76
5-21