Electra PXD912 Service Manual page 29

Pxd series r410a
Table of Contents

Advertisement

5.7
PXD15 ONG14 R410A
5.7.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
LEGEND
TC
Total Cooling Capacity, kW
SC
Sensible Capacity, kW
PI
Power Input, kW
WB –
Wet Bulb Temp., (
DB
Dry Bulb Temp., (
ID
Indoor
OU
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
SM PXD 1-E.3 GB
PERFORMANCE DATA & PRESSURE CURVES
ENTERING AIR WB/DB ID COIL ( °C)
DATA
15/21
TC
4.32
SC
2.74
0.96
PI
TC
4.18
2.69
SC
1.04
PI
TC
3.96
2.62
SC
1.12
PI
3.70
TC
2.54
SC
1.21
PI
TC
3.43
2.41
SC
1.31
PI
3.11
TC
2.27
SC
1.41
PI
TC
2.70
2.09
SC
1.54
PI
o
C)
o
C)
CONTENT
17/24
19/27
21/29
4.48
4.58
2.86
2.97
0.96
0.96
4.41
4.55
2.83
2.95
1.04
1.05
4.27
4.49
2.78
2.93
1.13
1.14
4.03
4.35
2.70
2.87
1.24
1.23
3.72
4.10
2.59
2.80
1.35
1.33
3.39
3.70
2.45
2.65
1.43
1.46
2.95
3.25
2.24
2.42
1.56
1.60
23/32
4.69
4.76
3.05
3.10
0.96
0.97
4.65
4.75
3.04
3.09
1.05
1.05
4.63
4.74
3.01
3.07
1.15
1.15
4.51
4.64
2.95
3.01
1.25
1.26
4.31
4.51
2.88
2.94
1.36
1.37
4.05
4.25
2.73
2.79
1.47
1.49
3.59
3.87
2.50
2.56
1.62
1.64
5-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents