Self-adhesive spacers are included with the TD 200 for mounting the TD 200 to a mounting
surface. The number of spacers you require depends on the thickness of the mounting
surface. Use the following steps to install the spacers.
1. Use the following guidelines to determine the number of spacers required for proper
mounting.
– One spacer for door thickness from 0.3 mm to 1.5 mm (0.01 in. to 0.06 in.)
– Two spacers on top of each other for door thickness of 1.5 mm to 4.0 mm
(0.06 in. to 0.16 in.)
2. Place the spacers over the screw holes on the inside of the backplate. The spacers
maintain pressure on the TD 200 circuit board when the TD 200 is reassembled. See
Figure 1-4.
Gasket
Frontplate
Figure 1-4

Positioning Spacers

Mounting the TD 200

Use the following steps and refer to Figure 1-4 to complete the mounting of your TD 200.
1. Place the supplied gasket on the frontplate of the TD 200.
2. Fit the frontplate into the cutout you made in the mounting surface.
3. Secure the backplate onto the frontplate of the TD 200 using the screws you removed
from the backplate. Tighten the screws.