Measurement Setup Differential Pressure - Vega VEGADIF 65 Operating Instructions Manual

Differential pressure transmitter with metallic measuring diaphragm
Table of Contents

Advertisement

4 Mounting
In gases and vapours
In vapour and conden-
sate plants
30
Fig. 27: Measurement setup with interface measurement
4.7 Measurement setup differential pressure
Mount VEGADIF 65 above the measurement loop so that con-
densate can drain off in the process cable.
Fig. 28: Measurement setup with differential pressure measurement between
two pipelines in gases and vapours
1
VEGADIF 65
2
3-fold valve block
3
Blocking valves
4
Pipelines
Mount VEGADIF 65 below the measurement loop so that some
condensate can collect in the effective pressure lines.
The ventilation is carried out via the ventilation valves on the instru-
ment, the 5-fold valve block enables blowing out the cables.
0,8
+
1,0
+
3
4
1
1
2
3
4
VEGADIF 65 • 4 ... 20 mA