4 Mounting

Suitability for the process
conditions
Suitability for the ambient
conditions
Moisture
Ventilation
16
4
Mounting
4.1

General instructions for use of the instrument

Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications or references in chapters "Techni-
cal data", "Dimensions, versions process component" and on the
nameplate.
The instrument is suitable for standard and extended ambient condi-
tions acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1.
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain off. This ap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.
To maintain the housing protection, make sure that the housing lid is
closed during operation and locked, if necessary.
Make sure that the degree of contamination specified in chapter
"Technical data" meets the existing ambient conditions.
The ventilation for the electronics housing is realised via a filter ele-
ment in the vicinity of the cable glands.
1
2
Fig. 9: Position of the filter element with single and double chamber housing
1
Filter element for ventilation of the electronics housing
2
Blind plug
Information:
Make sure that the filter element is always free of buildup during op-
eration. A high-pressure cleaner may not be used for cleaning.
1
1
2
2
2
1
VEGADIF 65 • 4 ... 20 mA