4 Mounting
In open vessels with ef-
fective pressure line
24
Fig. 18: Measurement setup, flow measurement in liquids
1
Orifice or impact pressure probe
2
Blocking valves
3
VEGADIF 65
4
Precipitator
5
Drain valves
6
3-fold valve block
4.5

Measurement setup level

.
Mount VEGADIF 65 below the lower measurement connection so
that the effective pressure lines are always filled with liquid
.
Minus side is open to the atmospheric pressure
.
When measuring liquids with solid content, the mounting of sepa-
rators and drain valves is useful to be able to avoid and remove
buildup.
min.
Fig. 19: Measurement setup, level measurement in the open vessel
1
VEGADIF 65
2
Minus side is open to the atmospheric pressure
3
Blocking valve
4
Precipitator
5
Drain valve
1
2
3
+
4
5
p
atm
+
p
atm
4
5
3
2
4
5
6
1
2
VEGADIF 65 • 4 ... 20 mA