Positioning The Stove - Morso 5660 Installation And Operating Instructions Manual

Standard insert
Table of Contents

Advertisement

1.4 Positioning the stove
CLEARANCE REQUIREMENTS TO COMBUSTIBLE SURFACES
The Morsø 5660 Standard NA is approved in the US and Canada for installation into the fol-
lowing;
1.
A masonry fireplace.
2.
Morsø Fireplace Insert Zero Clearance Enclosure (separate installations instructions
apply).
A
Sidewall to insert
B
Combustible mantel to insert
C
Top facing
D
Side facing
E
Hearth extension
F
Side facing, hearth extension
INSTALLLATION A
UNITED STATES
CANADA
*
When the appliance is elevated 6" (152 mm in Canada) or more above a combustible floor
(as measured from the floor to the bottom of the door glass), the floor in front of the fireplace
requires thermal protection equal to R-value =1.79 ft² °F h / BTU. Floor protection must
extend out minimum 21" (535 mm in Canada) and 8" (200mm in Canada) to each side of the
fuel loading door
When the appliance is elevated 20.25" (515mm in Canada) or more above a combustible floor
(as measured from the floor to the bottom of the door glass), the floor in front of the fireplace
requires non-combustible ember protection. Floor protection must extend out minimum of
16" (450 mm in Canada) and 8" (200 mm in Canada) to each side of the fuel loading door
12
13
B
17"
28½"
432 mm 724 mm 724 mm 200 mm below*
C
D
28½"
8"
E
F
See text 8"
203 mm