5.4.2

Configuring media redundancy

Configuring MRP
Proceed as follows to create a PROFINET IO configuration with MRP in STEP 7:
1. Generate a ring via the port interconnections in the topology view. First interconnect the
devices to a line topology. Connect the unassigned port of the last device in the line with
the unassigned port of the first device.
The following example shows one CPU 1516-3 PN/DP and two interface modules
IM 155-6 PN HF that are interconnected in a ring in the topology view of STEP 7.
Figure 5-35
2. Select the PROFINET IO system in the network view.
3. In the Inspector window, navigate to "Properties" > "General" > "PROFINET" > "MRP
domains" in the "Ring interconnections" field.
This field shows you all the topological rings in the IO system with the associated MRP
domains.
148
Configuring media redundancy
PROFINET with STEP 7 V14
Function Manual, 09/2016, A5E03444486-AG