Siemens SIMATIC PROFINET Function Manual page 140

With step 7 v14
Hide thumbs Also See for SIMATIC PROFINET:
Table of Contents

Advertisement

Functions
5.3 Shared device
MSI submodules
The input values of all channels are copied to a basic submodule and up to three other MSI
submodules during MSI configuration of an input module. The channels of the module are
then available with identical input values in the basic submodule and the MSI submodules.
The MSI submodules can be assigned to up to three IO controllers when the module is used
in a shared device. Each IO controller has read access to the same channels.
The following figure shows a digital input module with the basic submodule and three MSI
submodules. Each submodule is assigned to an IO controller. Diagnostics and parameter
assignment of the digital input module can be performed from the IO controller 1 via the
basic submodule.
Figure 5-30
Value status (Quality Information, QI)
The meaning of the value status depends on the submodule to which it pertains.
With basic submodule (= 1st submodule), the "0" value status indicates that the value is
incorrect.
With an MSI submodule (2nd to 4th submodule), the "0" value status indicates that the value
is incorrect or the basic submodule has not yet been configured (not ready).
140
Read access
Parameter assignment and system diagnostics
DI module with MSI submodules
PROFINET with STEP 7 V14
Function Manual, 09/2016, A5E03444486-AG

Hide quick links:

Advertisement

Table of Contents
loading