Omron CS1 Manual page 54

Multiple-application controllers with a wide range of functions
Hide thumbs Also See for CS1:
Table of Contents

Advertisement

● H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two Power Supply
Lines)
Applicable
Controller Link
SYSMAC LINK
Note: Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.
• Cable Length
The following cable lengths are available: 2 m, 5 m, 15 m, and
20 m. For lengths of 21 m or more, contact your OMRON sales
representative.
• Model Numbers
(1) 2 m, 5 m, 10 m, 15 m, 20 m
@@@
@@@
(e.g.)
S3200-CN
-20-25
(1)
(2)
(3)
( 2 ) Cable length
( 1 ) H-PCF
Optical Fiber Cable
@@@
Length
201
501
102
10m
152
15m
202
20m
Cable length
● GI Optical Cables
A qualified technician must select, assemble, and install GI
Optical Fiber Cable, so always let an optical cable specialist
handle the GI cable.
Usable Optical Fiber Cables and Optical Connectors
• Optical fiber types: Graded, indexed, multi-mode, all quartz
glass, fiber (GI-type AGF cable)
• Optical fiber construction (core diameter/clad diameter):
62.5/125 µm or 50/125 µm
• Optical fiber optical characteristics of optical fiber: Refer to the
tables.
• Optical connectors: ST connectors (IEC-874-10)
42
Programmable Controllers SYSMAC
Appearance
(2) 21 m or longer
(e.g.)
S3200-CN-20-20
(1)
(3) Specify the
cable length
in meters
( 3) Connectors (both ends)
No.
Connector lock
2m
20
5m
Full-lock
25
Half-lock
• Optical Connector Assembly Tool
Product
Applicable Units
name
This tool is used on site
for mounting crimp-cut
connectors and hard
Optical
plastic-clad silica optical
Fiber
fiber for optical
Assembly
transmission systems of
Tool *
SYSMAC C-series
SYSBUS, SYSMAC
LINK, and Controller
Link.
* There is a risk of quality problems when using cables assembled by typical
users, so we recommend purchasing cables with pre-attached connectors
or having a qualified technician assemble the cables.
• 50/125 µm AGF Cables
Items
Minimum Typical
Numerical
---
Aperture (N.A)
Transmission
---
loss (dB)
Connection
---
loss (dB)
Transmission
band width
500
(MHz·km)
Lf is Fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
• 62.5/125 µm AGF Cables
Items
Minimum Typical
Numerical
---
Aperture (N.A)
Transmission
---
loss (dB)
Connection
---
loss (dB)
Transmission
band width
200
(MHz·km)
Lf is Fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
CS1G/H
Model
S3200-CN@@@-20-20
S3200-CN@@@-20-25
S3200-CN@@@-25-25
Model
Maker
Sumitomo
Electric
CAK-0057
Industries,
Ltd.
Maximum
Remarks
0.21
---
---
0.5 km ≤ Lf
3.0Lf
0.2 km ≤ Lf ≤ 0.5 km
---
3.0 Lf + 0.2
Lf ≤ 0.2 km
3.0 Lf + 0.4
λ = 0.8 µm, one location
---
1.0
λ = 0.85 µm (LD)
---
---
Maximum
Remarks
0.28
---
---
0.5 km ≤ Lf
3.5Lf
0.2 km ≤ Lf ≤ 0.5 km
---
3.5Lf + 0.2
Lf ≤ 0.2 km
3.5Lf + 0.4
λ = 0.8 µm, one location
---
1.0
λ = 0.85 µm (LD)
---
---
Standards
---
Standards
---
λ = 0.8 µm,
Ta = 25°C
λ = 0.8 µm,
Ta = 25°C