Value: 11.943V
(Point 1)

Figure 60 LCD Display Pages 4-17, Readings

This is followed by the page shown in Figure 61, which displays detailed information for the optional timing control
module GPS receiver. The first two lines indicate the current latitude and longitude measurements in decimal degrees.
The third line is the current UTC time received from the GPS receiver. The forth line shows the number of satellites in
the solution, if time lock (TL) has been attained, position lock (PL) has been attained, and whether the timing control
module has locked onto the AC wave form from the main power input. If the optional GPS module is not installed, this
screen will indicate "GPS module not installed in the RMU".
Lat: 51.08548 N
Lon: 113.99714 W
04/22/09 15:28:26
GPS Sat: 12 TL PL AC

Figure 61 LCD Display Page 18, Timing Control Module Details

Next, the page shown in Figure 62 displays system fault information.
No faults

Figure 62 LCD Display Page 19, System Faults

The next page displayed on the LCD, as shown in Figure 63Error! Reference source not found., conveys information
on the software versions for various components in the RMU5.
Firmware Versions
OS: 1.06
APP:1.12
TCM:1.04
GPS:004
AIO:0.02

Figure 63 LCD Display Page 20, System Firmware Versions

The final page displayed on the LCD, as shown in Figure 64, provides identification information for the transceiver
currently connected to the RS-232 port. The information presented will aid in matching the transceiver to the
communications ESN used in corView.
RS-232 Port Info
EASYTRACK SERIAL
3110555

Figure 64 LCD Display Page 21, RS-232 Port Info

6.4 System Shutdown

When shutting down the RMU5 for repair or removal, it is necessary to follow this procedure:
1.
For safety, shutdown main power to the RMU5 and the monitored equipment using the master breaker at the
installation site.
2.
Disconnect the orange 24VAC/DC main power connector from the RMU5.
3.
Press and hold the RESET button for 10-15s, until the green PWR LED turns off.
MOBILTEX® DATA LTD.
Calgary, Alberta
TITLE:
RMU5 Generic Installation and Configuration Guide
DOCUMENT NO.:
SHEET:
RMU5-MAN-001
REV:
59 of 69