6.2.2 FTP Server
The FTP server is always enabled. Only the supervisor and administrator users have write access on the FTP server.
This gives access to firmware updates and retrieval of data log files. Use a standard FTP client to access this server.
Datalog files are stored in the "\Hard disk" folder if the internal flash drive option board is installed.
Firmware and configuration files are stored in the "\NORFlash" folder. Care must be taken with any changes made in
the "\NORFlash" directory, as the RMU5 application may cease to operate if incorrect changes are made to the directory.
6.2.3 Telnet Server
The Telnet server is always enabled. Only the administrator users have access to the Telnet server. The Telnet server
allows the user to execute other applications other than the standard RMU application. This will typically only be used
for system diagnostics and recovery if the main application is corrupted.
6.2.4 RMUSetup
If enabled in the RMU configuration at installation time, the RMU may be set up remotely over an Ethernet connection.
Operation of RMUSetup is identical to local configuration via USB, except for the connection step. Instead of selecting
the USB radio button, select the Ethernet button and enter the IP address of the RMU5 in the address box. Press the
"Connect" button to complete the connection to the RMU5.
6.3 LCD Display
The RMU5 LCD display allows for quick monitoring of the unit operation in the field without the need for a PC to be
attached. The display can be paged to various display screens using the 'UP' and 'DOWN' push buttons, located next
to the LCD display.
The first page, shown in Figure 57, is a quick glance status page that displays the DC measurements for the first four
analog measurement channels. Also displayed is the number of GPS satellites being received, or "NO GPS" if the
RMU5 is not equipped with the optional GPS receiver. Next, the signal strength (RSSI) for the satellite transceiver is
shown. Finally, the last line displays current status related to the satellite transceiver communications.
1:+11.95V
2:+0.010A
3:-0.050A
4:-2.560A
GPS:12
RSSI: 70%
RS-232 Comms Working
Figure 57 LCD Display Page 1, Main Status
The next page, shown in Figure 58, displays copyright information, and version information for the RMU5 operating
system and application software.
Mobiltex Data Ltd.
RMU5 (C)2007-2008
RMU Version 1.12
OS Version 1.06
Figure 58 LCD Display Page 2, Copyright and OS/Application Versions
This is followed by the page shown in Figure 59, which displays the real-time clock date/time, the IP address of the
Ethernet connection, and the ESN of the RMU5.
12/31/09 09:02:35
IP: 244.232.192.555
ESN 123456789
Figure 59 LCD Display Page 3, Real Time Clock, IP Address, and ESN
The next page, shown in Figure 60, displays the current reading for a measurement point. Thirteen sequential pages
display the present readings for CH1-4 DC, CH1-4 AC, backup battery, main supply voltage, temperature, main supply
current, and the isolated digital input. An additional number of readings pages may also be present if an analog channel
expansion unit is attached to the RMU5 sensor bus.
Base RMU I/O
CH1 DC
MOBILTEX® DATA LTD.
Calgary, Alberta
TITLE:
RMU5 Generic Installation and Configuration Guide
DOCUMENT NO.:
SHEET:
RMU5-MAN-001
REV:
58 of 69
1.10