Figure 41 Rmu5 Configuration - I/O Points Properties - Cortalk RMU5 Generic Installation And Configuration Manual

Table of Contents

Advertisement

Figure 41 RMU5 Configuration – I/O Points Properties
The current I/O point being operated on is selected by the "<<" and ">>" buttons next to the point number field. The
"I/O Points" parameters page contains the following fields for each I/O point:
3.
Name. This is a free form text field where the user can enter any pertinent information about the configuration in
the page. This field is purely informational and has no effect on the operation of the RMU5.
4.
Enable. This check box enables sampling of the selected I/O point.
5.
Data Source. This grouping of fields is used to indicate the physical source of data for the I/O point. For the built
in 10 I/O points, this information is hard coded. For expansion bus I/O points, these fields will be set according to
the I/O modules attached to the sensor expansion bus.
6.
I/O Type. This set of radio buttons determines the type for a particular I/O point. For the built in 10 I/O points,
this information is hard coded. For expansion bus I/O points, this field will be set according to the I/O modules
attached to the sensor expansion bus.
7.
Data Logging. The RMU5 is capable of recording measurements from each channel at a pre-determined interval.
The data is stored on a flash drive for later retrieval. For internal I/O points, the data may only be taken at periodic
intervals. For some sensor bus modules, it is possible to synchronize data sampling and logging to a programmed
offset from the edges of the interruption signal.
8.
Alarm Reporting. On communications systems where the RMU5 is able to initiate messages to the host, the RMU5
can be configured to send alarm reports when a given channel is outside allowable windows. Checking the Enable
checkbox enables a report to be sent when the channel enters the alarm state. Checking the Report on Return to
MOBILTEX® DATA LTD.
Calgary, Alberta
TITLE:
RMU5 Generic Installation and Configuration Guide
DOCUMENT NO.:
SHEET:
RMU5-MAN-001
REV:
42 of 69